Fault ride through capability improvement of DFIG based wind farm by fuzzy logic controlled parallel resonance fault current limiter

被引:71
作者
Rashid, Gilmanur [1 ]
Ali, Mohd Hasan [2 ]
机构
[1] ABB Inc, Senatobia, MS 38668 USA
[2] Univ Memphis, Dept Elect & Comp Engn, Memphis, TN 38152 USA
关键词
Bridge-type fault current limiter (BFCL); Doubly fed induction generator (DFIG); Fault ride through (FRT); Fuzzy logic controller (FLC); Grid code; Parallel resonance fault current limiter (PRFCL); Proportional-integral (PI) controller; Wind farm; ENERGY-CONVERSION SYSTEM; LOW-VOLTAGE RIDE; SIDE CONVERTER; ENHANCEMENT; GENERATOR; CROWBAR;
D O I
10.1016/j.epsr.2017.01.018
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Doubly fed induction generator (DFIG) based wind farms offer some distinct advantages, but their vulnerable nature to grid fault is problematic for the stable operation of power systems with higher Wind power penetration. Fault ride through (FRT) capability is a requirement imposed through the grid codes to ensure stable power system operation. A fuzzy logic controlled parallel resonance fault current limiter (FLC-PRFCL) is proposed to aid the DFIG based wind farms to achieve improved FRT capability. To check the effectiveness of the proposed FLC-PRFCL, temporary symmetric and asymmetric faults Were applied to the multi-machine system, to which a DFIG based wind farm is connected. The performance of the proposed FLC-PRFCL was compared with that of the crowbar, the bridge-type fault current limiter (BFCL) and conventional proportional-integral (PI) control based PRFCL (PI-PRFCL). Simulations were performed using the Matlab/Simulink Software. It was found that the proposed FLC-PRFCL is an effective device for FRT capability improvement of the DFIG based wind farm. Moreover, the proposed FLC-PRFCL outperforms the crowbar, the BFCL, and the PI-PRFCL. (C) 2017 Elsevier B.V. All rights reserved.
引用
收藏
页码:1 / 8
页数:8
相关论文
共 34 条
  • [1] Series Voltage Compensation for DFIG Wind Turbine Low-Voltage Ride-Through Solution
    Abdel-Baqi, Omar
    Nasiri, Adel
    [J]. IEEE TRANSACTIONS ON ENERGY CONVERSION, 2011, 26 (01) : 272 - 280
  • [2] Ali MH, 2012, WIND ENERGY SYSTEMS: SOLUTIONS FOR POWER QUALITY AND STABILIZATION, P1, DOI 10.1201/b11525
  • [3] Enhancement of transient stability by fuzzy logic-controlled SMES considering communication delay
    Ali, Mohd Hasan
    Park, Minwon
    Yu, In-Keun
    Murata, Toshiaki
    Tamura, Junji
    Wu, Bin
    [J]. INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2009, 31 (7-8) : 402 - 408
  • [4] A Low Component Count Series Voltage Compensation Scheme for DFIG WTs to Enhance Fault Ride-Through Capability
    Ambati, Bharath Babu
    Kanjiya, Parag
    Khadkikar, Vinod
    [J]. IEEE TRANSACTIONS ON ENERGY CONVERSION, 2015, 30 (01) : 208 - 217
  • [5] [Anonymous], GLOB WIND 2014 REP
  • [6] [Anonymous], 2012, Wind power in power systems
  • [7] Boldea Ion, 2014, 2014 17th International Conference on Electrical Machines and Systems (ICEMS), P1, DOI 10.1109/ICEMS.2014.7013919
  • [8] Overview of Control Systems for the Operation of DFIGs in Wind Energy Applications
    Cardenas, Roberto
    Pena, Ruben
    Alepuz, Salvador
    Asher, Greg
    [J]. IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2013, 60 (07) : 2776 - 2798
  • [9] General Atomics Electronics Systems, 2016, HIGH VOLT CAP POW SU
  • [10] LVRT Capability of DFIG-Based WECS Under Asymmetrical Grid Fault Condition
    Geng, Hua
    Liu, Cong
    Yang, Geng
    [J]. IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2013, 60 (06) : 2495 - 2509