Impact Analysis of Static Voltage Assessment Based on Three-Phase Probabilistic Load Flow with Correlated Wind Power

被引:0
|
作者
Ran, Xiaohong [1 ]
Bai, Zhan [2 ]
机构
[1] Wuhan Univ, Sch Elect Engn, Wuhan 430072, Peoples R China
[2] Huazhong Univ Sci & Technol, Sch Elect & Elect Engn, Wuhan 430074, Peoples R China
关键词
probabilistic load flow; static voltage assessment; improved cumulants method; correlation; Cornish-Fisher expansion; POINT ESTIMATE METHOD; DISTRIBUTION-SYSTEMS; RECONFIGURATION; CAPABILITY;
D O I
10.1002/tee.22365
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Impact analysis based on the three-phase probabilistic load flow (PLF) algorithm is proposed in this paper to evaluate the effect on static voltage of an unbalanced power system. Correlations between adjacent wind power resources are considered. An improved cumulants method with correlated variables is proposed and applied to the unbalanced system. Cornish-Fisher expansion is used to obtain the cumulative distribution function of bus voltage and line flow. The impacts for wind turbines , which include rated capacity, power factor, and correlation on PLF, are studied, and the relations of the means and standard deviations between three-phase unbalanced and balanced systems are analyzed. A 25-bus and a 33-bus system are studied as examples to show the effectiveness of proposed method, and results of cumulants method are compared with those of Monte Carlo simulations. (c) 2016 Institute of Electrical Engineers of Japan. Published by John Wiley & Sons, Inc.
引用
收藏
页码:185 / 194
页数:10
相关论文
共 50 条