Static synchronous compensator sizing for enhancement of fault ride-through capability and voltage stabilisation of fixed speed wind farms

被引:34
作者
Mahfouz, M. M. A. [1 ]
El-Sayed, Mohamed A. H. [2 ]
机构
[1] Helwan Univ, Elect Power & Machines Dept, Cairo, Egypt
[2] Kuwait Univ, Coll Engn & Petr, Safat, Kuwait
关键词
asynchronous generators; electric current control; flexible AC transmission systems; invertors; power generation faults; power generation planning; power transmission planning; reactive power control; robust control; wind power plants; static synchronous compensator sizing; fault ride-through capability; voltage stabilisation; fixed speed wind farms; wind energy affects; power systems; FACT devices; static synchronous compensator; three-level inverter; STATCOM rating; voltage-level regulation; vector current control; reactive power; torque speed curve analysis; induction generator speed limit; critical clearing time; low-voltage ride-through capability; system planner; STATCOM; SERIES;
D O I
10.1049/iet-rpg.2012.0365
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
High penetration level of wind energy affects the generation profile of the power systems, which impose more stringent connection requirements of wind farms. The ability of wind power plant to remain connected during grid faults is very important to avoid cascaded outages because of power deficit. FACT devices are considered to be a key technology to accomplish these requirements. The implementation of three-level inverter based on a static synchronous compensator (STATCOM) for the improvement of the ride-through and stability of fixed speed wind farms is analysed here. This brings the challenges for system planner to determine the appropriate STATCOM rating. This study provides a simple approach to evaluate the STATCOM rating for voltage-level regulation at the point of common coupling around its pre-specified value. Vector current control is used as robust control to inject the required reactive power from STATCOM. This study emphasizes also on the analysis of torque speed curve to evaluate the induction generator speed limit and for defining the critical clearing time of the fault according to the selected STATCOM rating. Simulation results under fault conditions are performed to validate the enhancement of wind farm low-voltage ride-through capability and increasing the critical clearing time by installing STATCOM.
引用
收藏
页码:1 / 9
页数:9
相关论文
共 7 条
[1]  
[Anonymous], INT J ELECT COMPUT S
[2]   Fault ride-through of large wind farms using series dynamic braking resistors (March 2007) [J].
Causebrook, Andrew ;
Atkinson, David J. ;
Jack, Alan G. .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2007, 22 (03) :966-975
[3]   Transient stability assessment of power systems containing series and shunt compensators [J].
Chatterjee, Dheeman ;
Ghosh, Arindam .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2007, 22 (03) :1210-1220
[4]  
Chompoo C., 2005, IEEE T IND APPL, V41, P668
[5]   Low voltage ride through of wind farms with cage generators: STATCOM versus SVC [J].
Molinas, Marta ;
Suul, Jon Are ;
Undeland, Tore .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2008, 23 (03) :1104-1117
[6]   Modeling, analysis, and control of a current source inverter-based STATCOM [J].
Shen, D ;
Lehn, PW .
IEEE TRANSACTIONS ON POWER DELIVERY, 2002, 17 (01) :248-253
[7]   Response of Fixed Speed Wind Turbines to System Frequency Disturbances [J].
Sumper, Andreas ;
Gomis-Belimunt, Oriol ;
Sudria-Andreu, Antoni ;
Villafafila-Robles, Roberto ;
Rull-Duran, Joan .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2009, 24 (01) :181-192