Self-tuned fuzzy-proportional-integral compensated zero/minimum active power algorithm based dynamic voltage restorer

被引:14
作者
Mallick, Nirmalya [1 ]
Mukherjee, Vivekananda [1 ]
机构
[1] Indian Inst Technol, Indian Sch Mines, Dept Elect Engn, Dhanbad, Jharkhand, India
关键词
induction motors; power factor; starting; fault simulation; power control; voltage control; fuzzy control; PI control; load regulation; electric current control; machine control; self-tuned fuzzy-proportional-integral compensation; voltage sag mitigation; power quality problem; direct-on-line starting; three-phase induction motor; IM; three-phase short circuit faults; real power optimised dynamic voltage restorer; DVR; reduced power factor strategy; fuzzy-proportional-integral based self-tuned control methodology; load voltage regulation; direct current link voltage; zero-minimum active power algorithm; DVR; SCHEME; SAGS;
D O I
10.1049/iet-gtd.2017.1170
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Voltage sag is the most common and severe power quality problem in the recent times due to its detrimental effects on modern sensitive equipment. Generally, direct-on-line starting of the three-phase induction motor (IM) and various kinds of short circuit fault are directly responsible for this event. This study investigates the impacts of starting and stopping of two three-phase IMs on the load voltage profile. To be more critical, two three-phase short circuit faults and one unsymmetrical fault are also simulated in the same network at different instants of time. A simple control algorithm of a real power optimised dynamic voltage restorer (DVR) with a reduced power factor strategy is presented to protect the sensitive load from these types of detrimental events. A novel fuzzy-proportional-integral based self-tuned control methodology is implemented in the proposed work to compensate the loss in the DVR circuit as well as to regulate the load voltage and the direct current link voltage. The results show the effectiveness of the adopted control scheme in DVR application to mitigate the voltage sag.
引用
收藏
页码:2778 / 2787
页数:10
相关论文
共 24 条
[1]   Minimum power operation of cascade inverter-based dynamic voltage restorer [J].
Al-Hadidi, H. K. ;
Gole, A. M. ;
Jacobson, David A. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2008, 23 (02) :889-898
[2]  
[Anonymous], IEEE SPECTR
[3]  
[Anonymous], 2015, INT J ELECT ELECT DA
[4]  
[Anonymous], 2002, POWER QUALITY ENHANC
[5]  
[Anonymous], P INT C EL MACH SYST
[6]  
[Anonymous], P NAT POW EN C KUAL
[7]  
[Anonymous], P IEEE POW ENG SOC W
[8]  
[Anonymous], P IND APPL C SALT LA
[9]  
Bollen M.H., 1999, UNDERSTANDING POWER
[10]   Influence of voltage dips on industrial equipment: Analysis and assessment [J].
Honrubia-Escribano, A. ;
Gomez-Lazaro, E. ;
Molina-Garcia, A. ;
Fuentes, J. A. .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2012, 41 (01) :87-95