A Time-Domain AC Electric Arc Furnace Model for Flicker Planning Studies

被引:36
|
作者
Horton, Randy [1 ]
Haskew, Timothy A. [2 ]
Burch, Reuben F., IV [1 ]
机构
[1] Alabama Power Co, Birmingham, AL 35291 USA
[2] Auburn Univ, Auburn, AL 35291 USA
关键词
Flicker; flicker measurement; flicker transfer coefficient; furnaces; power quality;
D O I
10.1109/TPWRD.2008.2007021
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
A time-domain model of an AC electric arc furnace (EAF) was developed for power system (flicker) planning studies. The proposed model was implemented in the Electro Magnetic Transient Program (EMTP), and it focuses on the behavior of the EAF during the early stages of the melt cycle, thus providing an accurate prediction of the short term flicker created by the EAF, specifically P-st9%.. The primary advantages of the proposed model over existing models are: 1) it uses system data that is readily available to the planning engineer; 2) it is a three phase model and can accurately model imbalance and predict flicker at the point of common coupling (PCC) as well as remote buses in the power system; and 3) its accuracy has been verified using synchronized flicker measurements of an actual EAF. Existing time-domain EAF models that are used in flicker planning studies require measurement or statistical data that is difficult to obtain during the planning stages of a project. Frequency domain methods are a popular means of estimating the flicker created by an EAF; however, when these methods are used in flicker planning studies, the operational uncertainty of the EAF introduces error into the calculations. Also, in many cases, frequency domain methods struggle to accurately predict the flicker level at buses remote from the PCC. Thus, a time-domain EAF model which can accurately predict P-st99% at points of interest and uses readily available system information is needed. The following paper describes such an EAF model. Validation of the proposed model is performed by comparing simulation results with flicker measurements of an actual EAF that were time synchronized using global positioning systems (GPS).
引用
收藏
页码:1450 / 1457
页数:8
相关论文
共 50 条
  • [1] Flicker characteristic estimation of an AC electric arc furnace
    Lu, CW
    Huang, SJ
    Huang, CL
    ELECTRIC POWER SYSTEMS RESEARCH, 2000, 54 (02) : 121 - 130
  • [2] A new time domain model for electric arc furnace
    Hooshmand, Rahmatollah
    Banejad, Mahdi
    Esfahani, Mahdi Torabian
    JOURNAL OF ELECTRICAL ENGINEERING-ELEKTROTECHNICKY CASOPIS, 2008, 59 (04): : 195 - 202
  • [3] A Practical Electric Arc Furnace Model For Flicker Assessment
    Pereira Rosentino Junior, Arnaldo Jose
    Gondim, Isaque Nogueira
    Macedo Junior, Jose Rubens
    Delaiba, Antonio Carlos
    JOURNAL OF CONTROL AUTOMATION AND ELECTRICAL SYSTEMS, 2015, 26 (01) : 68 - 79
  • [4] An electric arc model of AC electric arc furnace for research on voltage fluctuation
    Wang, Yan
    Mao, Zhi-Zhong
    Li, Yan
    Tian, Hui-Xin
    Yuan, Ping
    Dianwang Jishu/Power System Technology, 2010, 34 (01): : 36 - 40
  • [5] A novel chaotic model of AC electric arc furnace for power quality studies
    Wang, Y. F.
    Jiang, J. G.
    2007 INTERNATIONAL CONFERENCE ON ELECTRICAL MACHINES AND SYSTEMS, VOLS 1-4, 2007, : 767 - 770
  • [6] A hybrid simulation model of AC electric arc furnace
    Li Hongru
    Zhao Haoyi
    Li Fangyan
    Qiu Bo
    PROCEEDINGS OF THE 2012 24TH CHINESE CONTROL AND DECISION CONFERENCE (CCDC), 2012, : 188 - 193
  • [7] A new time domain arc model for arc furnace
    Wang, Yan
    Mao, Zhi-Zhong
    Li, Yan
    Tian, Hui-Xin
    Dongbei Daxue Xuebao/Journal of Northeastern University, 2009, 30 (04): : 487 - 490
  • [8] New Time Domain Electric Arc Furnace Model for Power Quality Study
    Bhonsle, Deepak C.
    Kelkar, Ramesh B.
    2014 IEEE 6TH INDIA INTERNATIONAL CONFERENCE ON POWER ELECTRONICS (IICPE), 2014,
  • [9] Stochastic model of AC electric arc furnace based on MATLAB
    Department of Electrical Engineering, Shanghai Jiao Tong University, Shanghai 200240, China
    Gaodianya Jishu/High Voltage Engineering, 2008, 34 (05): : 973 - 977
  • [10] Flicker characteristic estimation of an electric arc furnace feeder
    Chen, MT
    Lu, CW
    Huang, CL
    POWERCON '98: 1998 INTERNATIONAL CONFERENCE ON POWER SYSTEM TECHNOLOGY - PROCEEDINGS, VOLS 1 AND 2, 1998, : 58 - 63