Apparatus for Online Power Transformer Winding Monitoring Using Bushing Tap Injection

被引:87
|
作者
De Rybel, Tom [1 ]
Singh, Arvind [1 ]
Vandermaar, John A. [2 ]
Wang, May [2 ]
Marti, Jose R. [1 ]
Srivastava, K. D. [1 ]
机构
[1] Univ British Columbia, Dept Elect & Comp Engn, Vancouver, BC V6T 1Z4, Canada
[2] PowerTech Labs Inc, Surrey, BC V3W 7R7, Canada
关键词
Bushing tap injection; frequency response; frequency-response analysis (FRA); online diagnostics; power transformers; swept frequency-response analysis (SFRA); transmission-line diagnostics (TLD); winding signature;
D O I
10.1109/TPWRD.2009.2022674
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Online transformer condition monitoring techniques based on transfer function methods, such as transmission-line diagnostics and swept frequency-response analysis, require the injection of a known test signal into the transformer. On larger power transformers, a practical method is to use the available bushing tap connection. In this paper, we will discuss a custom high-power signal generator that injects high-frequency signals on the bushing tap of the transformer under investigation, as well as a circuit to replace the bushing tap short and allow online operation of the system. Finally, the system is demonstrated on a 650 kV transformer.
引用
收藏
页码:996 / 1003
页数:8
相关论文
共 50 条
  • [41] Recognition of power transformer winding movement and deformation using FRA
    Saied, Mohamed M.
    Al-Shaher, Meshal A.
    COMPEL-THE INTERNATIONAL JOURNAL FOR COMPUTATION AND MATHEMATICS IN ELECTRICAL AND ELECTRONIC ENGINEERING, 2007, 26 (05) : 1392 - 1410
  • [42] Power Transformer Winding Fault Analysis using Transfer Function
    Patel, Kalpana
    Das, Narottam
    Abu-siada, A.
    Islam, Syed
    2013 AUSTRALASIAN UNIVERSITIES POWER ENGINEERING CONFERENCE (AUPEC), 2013,
  • [43] On-line Monitoring Of Winding Deformation Of Power Transformer Based On ARM And FPGA
    Zhang Shan
    Cai Zhenjiang
    Zhang Dening
    Kou Hongjuan
    Guo Jinwei
    2009 INTERNATIONAL CONFERENCE ON MEASURING TECHNOLOGY AND MECHATRONICS AUTOMATION, VOL II, 2009, : 657 - +
  • [44] Simulation Test Method for Vibration Monitoring Research on Winding Looseness of Power Transformer
    Li, Kai
    Xu, Honghua
    Li, Yong
    Zhou, Yu
    Ma, Hongzhong
    Liu, Jiufu
    Gong, Jiewei
    2014 INTERNATIONAL CONFERENCE ON POWER SYSTEM TECHNOLOGY (POWERCON), 2014, : 1602 - 1608
  • [45] Design and implementation of online vibration monitoring system for power transformer
    Zhou, Qiukuan
    Wan, Junbiao
    Wang, Fenghua
    Xu, Chenbo
    Dianli Zidonghua Shebei/Electric Power Automation Equipment, 2014, 34 (03): : 162 - 166
  • [46] Detection of Power Transformer Bushing Faults and Oil Degradation using Frequency Response Analysis
    Hashemnia, Naser
    Abu-Siada, A.
    Islam, S.
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2016, 23 (01) : 222 - 229
  • [47] Online Monitoring Technology of Power Transformer based on Vibration Analysis
    Meng, Junhong
    Singh, Maninder
    Sharma, Manish
    Singh, Daljeet
    Kaur, Preet
    Kumar, Rajeev
    JOURNAL OF INTELLIGENT SYSTEMS, 2021, 30 (01) : 554 - 563
  • [48] Hardware Design of Online Monitoring System for Power Transformer Malfunction
    Zhang, Zhan
    Gao, Caixia
    ELECTRICAL INFORMATION AND MECHATRONICS AND APPLICATIONS, PTS 1 AND 2, 2012, 143-144 : 618 - 621
  • [49] Switched Ethernet Based Online Monitoring System for Power Transformer
    Li Ming
    2011 30TH CHINESE CONTROL CONFERENCE (CCC), 2011, : 5253 - 5257
  • [50] Application research on online monitoring of deformation of windings of power transformer
    Xu, D.K.
    Li, Y.M.
    Gaodianya Jishu/High Voltage Engineering, 2001, 27 (04):