Apparatus for Online Power Transformer Winding Monitoring Using Bushing Tap Injection

被引:87
|
作者
De Rybel, Tom [1 ]
Singh, Arvind [1 ]
Vandermaar, John A. [2 ]
Wang, May [2 ]
Marti, Jose R. [1 ]
Srivastava, K. D. [1 ]
机构
[1] Univ British Columbia, Dept Elect & Comp Engn, Vancouver, BC V6T 1Z4, Canada
[2] PowerTech Labs Inc, Surrey, BC V3W 7R7, Canada
关键词
Bushing tap injection; frequency response; frequency-response analysis (FRA); online diagnostics; power transformers; swept frequency-response analysis (SFRA); transmission-line diagnostics (TLD); winding signature;
D O I
10.1109/TPWRD.2009.2022674
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Online transformer condition monitoring techniques based on transfer function methods, such as transmission-line diagnostics and swept frequency-response analysis, require the injection of a known test signal into the transformer. On larger power transformers, a practical method is to use the available bushing tap connection. In this paper, we will discuss a custom high-power signal generator that injects high-frequency signals on the bushing tap of the transformer under investigation, as well as a circuit to replace the bushing tap short and allow online operation of the system. Finally, the system is demonstrated on a 650 kV transformer.
引用
收藏
页码:996 / 1003
页数:8
相关论文
共 50 条
  • [1] The Application of Bushing Tap Method in the Transformer Winding Deformation Test
    Wang Wei
    Jin Xin
    Zhu Yuanda
    Yin Yongfei
    Zhang Su
    Shi Xingcai
    Jin Yi
    Xu Minghu
    Zhao Hui
    Liu Jun
    PROCEEDINGS OF THE 2015 INTERNATIONAL CONFERENCE ON INTELLIGENT SYSTEMS RESEARCH AND MECHATRONICS ENGINEERING, 2015, 121 : 2035 - 2038
  • [2] Monitoring of winding deformation of Power transformer by using nanosecond pulses
    Liu Hualin
    Zhan Yinbo
    Lei Xiao
    Wang Youyuan
    Zeng Huarong
    Li Jian
    MEASURING TECHNOLOGY AND MECHATRONICS AUTOMATION IV, PTS 1 AND 2, 2012, 128-129 : 190 - +
  • [3] A method for modeling power transformer tap winding for transient studies
    Naderi, MS
    Vakilian, M
    CONFERENCE RECORD OF THE 2004 IEEE INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATION, 2004, : 34 - 37
  • [4] An Improved Transformer Winding Tap Injection DSTATCOM Topology for Medium-Voltage Reactive Power Compensation
    Lei, Ertao
    Yin, Xianggen
    Zhang, Zhe
    Chen, Yu
    IEEE TRANSACTIONS ON POWER ELECTRONICS, 2018, 33 (03) : 2113 - 2126
  • [5] Field validation tests of the TLD box for online power transformer winding monitoring systems
    Singh, Arvind
    De Rybel, Tom
    Marti, Jose. R.
    Srivastava, K. D.
    2007 CANADIAN CONFERENCE ON ELECTRICAL AND COMPUTER ENGINEERING, VOLS 1-3, 2007, : 141 - 144
  • [6] Apparatus for On-line Monitoring of Transformer Winding Deformation using Leakage Inductance Identification
    Yao Zhoufei
    Yin Yi
    Wang Zhihao
    Li Zhe
    Wang Qiaohua
    PROCEEDINGS OF 2012 IEEE INTERNATIONAL CONFERENCE ON CONDITION MONITORING AND DIAGNOSIS (IEEE CMD 2012), 2012, : 613 - 616
  • [7] Online monitoring and diagnosis method of transformer winding deformation
    Wu, Hao
    Wang, Xue
    Zhang, Jiajia
    IEEJ TRANSACTIONS ON ELECTRICAL AND ELECTRONIC ENGINEERING, 2019, 14 (12) : 1747 - 1753
  • [8] CORONA MEASUREMENT ON HIGH-VOLTAGE APPARATUS USING BUSHING CAPACITANCE TAP
    BROWN, RD
    IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1965, PA84 (08): : 667 - &
  • [9] TRANSFORMER CORONA MEASUREMENT USING CONDENSER BUSHING TAP AND RESONANT MEASURING CIRCUITS
    NARUBT, P
    IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1965, PA84 (08): : 652 - &
  • [10] New-style dielectric loss of transformer bushing on-line monitoring apparatus
    Huang, Xin-Bo
    Wang, Zhuo
    Wang, Hong-Liang
    Wang, Hong
    Advances in Information Sciences and Service Sciences, 2012, 4 (23): : 215 - 223