共 50 条
New Fault-Location Algorithm for Series-Compensated Double-Circuit Transmission Line
被引:0
|作者:
Cai, Daiying
[1
,2
]
Zhang, Jun
[1
,2
]
机构:
[1] Chongqing Univ Posts & Telecommun, Chongqing Key Lab Complex Syst & Bion Control, Chongqing 400065, Peoples R China
[2] Chongqing Univ Posts & Telecommun, Smart Energy Res Ctr, Chongqing 400065, Peoples R China
来源:
IEEE ACCESS
|
2020年
/
8卷
关键词:
Circuit faults;
Power transmission lines;
Voltage measurement;
Transmission line measurements;
Impedance;
Capacitors;
Synchronization;
Keyword series-compensated double-circuit transmission line;
fault-location;
six-sequence component transformation;
metal oxide varistor (MOV);
series capacitors (SCs);
D O I:
10.1109/ACCESS.2020.3039877
中图分类号:
TP [自动化技术、计算机技术];
学科分类号:
0812 ;
摘要:
This paper proposes a new fault location algorithm to accurately locate the faults of series-compensated double-circuit transmission line and improve the stability of power system operation, which is not affected by fault types. The proposed algorithm is based on asynchronous voltage and current at both ends of the line, the pre-fault voltage and current are used to synchronize time. The six-sequence component transformation is introduced, and with the help of the phase-sequence selection rule, the proposed algorithm eliminates the non-linear impedance of metal oxide varistor (MOV). Simultaneously, to confirm the robustness of the algorithm, different fault types, different fault initial angles and different fault resistances are taken into account in the system simulation. Not only that, the influence of series capacitors (SCs) installation positions, line parameter errors, different sampling rates and measurement errors are also tested. In general, the proposed fault-location algorithm has excellent performance. PSCAD/EMTDC and MATLAB are used in simulation studies, the results show that the maximum estimated error of fault-location does not exceed 1.8631%.