Computational analysis of reduced-mixing personal ventilation jets

被引:43
作者
Russo, Jackie S. [1 ]
Dang, Thong Q. [1 ]
Khalifa, H. Ezzat [1 ]
机构
[1] Syracuse Univ, Syracuse, NY 13244 USA
基金
美国国家环境保护局;
关键词
Air quality; Ventilation; Personalized ventilation; ROOM;
D O I
10.1016/j.buildenv.2008.11.005
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
In this paper we develop a detailed computational fluid dynamics (CFD) model of a personal ventilation (PV) setup comprising a PV nozzle, seated thermal manikin and floor diffuser, then use experimental velocity and tracer gas concentration data for the same setup to validate the CFD model. Specifically, we compare CFD results with the experimental results obtained with both a conventional round nozzle and a novel low-mixing co-flow nozzle directing a PV fresh air jet toward the breathing zone (BZ) of a seated thermal manikin in a thermally controlled chamber ventilated also by a floor diffuser behind the manikin. The CFD model shows excellent agreement with the experimental data. We then exercise the CFD model to study the effect of nozzle exit boundary conditions such as turbulence intensity and length scale, flow rate and temperature, and manikin temperature on the air quality in the BZ of the heated manikin. It is shown that the air quality of the novel PV system is sensitive to the nozzle exit turbulence intensity and flow rate, and insensitive to jet temperature within the 20-26 degrees C range, and to body temperature within a clo range of 0-1.A companion paper presents in detail the experimental set up and results used to validate the CFD model discussed in this paper. (C) 2008 Elsevier Ltd. All rights reserved.
引用
收藏
页码:1559 / 1567
页数:9
相关论文
共 27 条
[1]  
*ANSI ASHRAE, 2004, 6212004 ANSI ASHRAE
[2]  
Awbi H.B., 2003, Ventilation of Buildings
[3]  
Bolashikov Z., 2003, HLTH BUILDINGS 2003, P850
[4]   Performance of personalized ventilation in conjunction with mixing and displacement ventilation [J].
Cermak, R ;
Melikov, AK ;
Forejt, L ;
Kovar, O .
HVAC&R RESEARCH, 2006, 12 (02) :295-311
[5]  
Cermak R, 2003, P HLTH BUILDINGS, V2, P486
[6]  
DYGERT R, ASHRAE T IN PRESS, V115
[7]   INDOOR AIR-FLOW AND POLLUTANT REMOVAL IN A ROOM WITH FLOOR-BASED TASK VENTILATION - RESULTS OF ADDITIONAL EXPERIMENTS [J].
FAULKNER, D ;
FISK, WJ ;
SULLIVAN, DP .
BUILDING AND ENVIRONMENT, 1995, 30 (03) :323-332
[8]  
Faulkner D., 2002, VENTILATION EFFICIEN
[9]  
FAULKNER D, 1999, LBNL42597 IND ENV DE
[10]  
FAULKNER D, 2000, LBNL42700 IND ENV DE