Theoretical analysis of a CO2-NH3 cascade refrigeration system for cooling applications at low temperatures

被引:133
作者
Dopazo, J. Alberto [1 ]
Fernandez-Seara, Jose [1 ]
Sieres, Jaime [1 ]
Uhia, Francisco J. [1 ]
机构
[1] Univ Vigo, ETS Ingenieros Ind, Area Maquinas & Motores Term, Vigo 36310, Spain
关键词
Cascade refrigeration; Compression system; CO2-NH3; Natural refrigerants; Optimization; DESIGN;
D O I
10.1016/j.applthermaleng.2008.07.006
中图分类号
O414.1 [热力学];
学科分类号
摘要
As a result of environmental problems related to global warming and depletion of the ozone layer caused by the use of synthetic refrigerants (CFC's, HCFC's and HFC's) experienced over the last decades, the return to the use of natural substances for refrigeration purposes, appears to be the best long-term alternative. In this paper, a cascade refrigeration system with CO2 and NH3 as working fluids in the low and high temperature stages, respectively, has been analysed. Results of COP and exergetic efficiency versus operating and design parameters have been obtained. In addition, an optimization study based on the optimum CO2 condensing temperature has been done. Results show that following both method's exergy analysis and energy optimization, an optimum value of condensing CO2 temperature is obtained. The compressor isentropic efficiency influence on the optimum system COP has been demonstrated. A methodology to obtain relevant diagrams and correlations to serve as a guideline for design and optimization of this type of systems has been developed and it is presented in the paper. (C) 2008 Elsevier Ltd. All rights reserved.
引用
收藏
页码:1577 / 1583
页数:7
相关论文
共 26 条
  • [1] [Anonymous], 2001, P 2001 ASME INT MECH
  • [2] Optimization of a CO2-C3H8 cascade system for refrigeration and heating
    Bhattacharyya, S
    Mukhopadhyay, S
    Kumar, A
    Khurana, RK
    Sarkar, J
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2005, 28 (08): : 1284 - 1292
  • [3] The optimum high pressure for CO2 transcritical refrigeration systems with internal heat exchangers
    Chen, Y
    Gu, JJ
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2005, 28 (08): : 1238 - 1249
  • [4] Particular characteristics of transcritical CO2 refrigeration cycle with an ejector
    Deng, Jian-qiang
    Jiang, Pei-xue
    Lu, Tao
    Lu, Wei
    [J]. APPLIED THERMAL ENGINEERING, 2007, 27 (2-3) : 381 - 388
  • [5] Eggen G, 1998, REFR SCI T, V1998, P281
  • [6] Compression-absorption cascade refrigeration system
    Fernández-Seara, J
    Sieres, J
    Vázquez, M
    [J]. APPLIED THERMAL ENGINEERING, 2006, 26 (5-6) : 502 - 512
  • [7] GROLL E, 2000, COMPR ENG C PURD, P43
  • [8] HRNJAK P, 2000, 4 IIR GUST LOR NAT W, P9
  • [9] Hwang Y., 1999, ASHRAE T, V105
  • [10] Fundamental process and system design issues in CO2 vapor compression systems
    Kim, MH
    Pettersen, J
    Bullard, CW
    [J]. PROGRESS IN ENERGY AND COMBUSTION SCIENCE, 2004, 30 (02) : 119 - 174