A heat pump driven and hollow fiber membrane-based liquid desiccant air dehumidification system: Modeling and experimental validation

被引:89
作者
Zhang, Li-Zhi [1 ,2 ]
Zhang, Ning [1 ]
机构
[1] S China Univ Technol, Key Lab Enhanced Heat Transfer & Energy Conservat, Educ Minist, Sch Chem & Chem Engn, Guangzhou 510640, Guangdong, Peoples R China
[2] S China Univ Technol, State Key Lab Subtrop Bldg Sci, Guangzhou 510640, Guangdong, Peoples R China
关键词
Heat pump; Hollow fiber membrane; Liquid desiccant; Air dehumidification system; MASS-TRANSFER; PERFORMANCE; HUMIDIFICATION; REGENERATION; SIMULATION; CHILLERS; MODULE;
D O I
10.1016/j.energy.2013.10.014
中图分类号
O414.1 [热力学];
学科分类号
摘要
A compression heat pump driven and membrane-based liquid desiccant air dehumidification system is presented. The dehumidifier and the regenerator are made of two hollow fiber membrane bundles packed in two shells. Water vapor can permeate through these membranes effectively, while the liquid desiccant droplets are prevented from cross-over. Simultaneous heating and cooling of the salt solution are realized with a heat pump system to improve energy efficiency. In this research, the system is built up and a complete modeling is performed for the system. Heat and mass transfer processes in the membrane modules, as well as in the evaporator, the condenser, and other key components are modeled in detail. The whole model is validated by experiment. The performances of SDP (specific dehumidification power), dehumidification efficiency, EER (energy efficiency ratio) of heat pump, and the COP (coefficient of performance) of the system are investigated numerically and experimentally. The results show that the model can predict the system accurately. The dehumidification capabilities and the energy efficiencies of the system are high. Further, it performs well even under the harsh hot and humid South China weather conditions. (C) 2013 Elsevier Ltd. All rights reserved.
引用
收藏
页码:441 / 451
页数:11
相关论文
共 25 条
[1]  
[Anonymous], 2002, NIST reference fluid thermodynamic and transport properties REFPROP
[2]  
[Anonymous], 2007, Introduction to Heat Transfer
[3]   Heat and Mass Transfer between Air and Liquid Desiccant in Cross-flow Contact Systems [J].
Babakhani, Davoud ;
Soleymani, Meysam ;
Moheb, Ahmad .
CHEMICAL ENGINEERING & TECHNOLOGY, 2010, 33 (02) :281-291
[4]   Steady-state model of centrifugal liquid chillers [J].
Browne, MW ;
Bansal, PK .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 1998, 21 (05) :343-358
[5]  
Ding GL., 2001, SIMULATION OPTIMIZAT
[6]   Modelling of reciprocating and scroll compressors [J].
Duprez, Marie-Eve ;
Dumont, Eric ;
Frere, Marc .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2007, 30 (05) :873-886
[7]   Steady-state simulation of screw liquid chillers [J].
Fu, L ;
Ding, GL ;
Su, ZJ ;
Zhao, GQ .
APPLIED THERMAL ENGINEERING, 2002, 22 (15) :1731-1748
[8]   Study of an aqueous lithium chloride desiccant system: Air dehumidification and desiccant regeneration [J].
Fumo, N ;
Goswami, DY .
SOLAR ENERGY, 2002, 72 (04) :351-361
[9]  
Guttman I., 1965, Introductory engineering statistics
[10]   A simple dynamic model of cooling coil unit [J].
Jin, GY ;
Cai, WH ;
Wang, YW ;
Yao, Y .
ENERGY CONVERSION AND MANAGEMENT, 2006, 47 (15-16) :2659-2672