Influence of charging voltage magnitude on time domain dielectric response of oil-paper insulation

被引:6
作者
Banerjee, Chandra Madhab [1 ]
Dutta, Saurabh [1 ]
Beret, Arijit [1 ]
Chakravorti, Sivaji [2 ]
机构
[1] Indian Sch Mines, Indian Inst Technol, Dept Elect Engn, Dhanbad 826004, Jharkhand, India
[2] Jadavpur Univ, Dept Elect Engn, Kolkata, W Bengal, India
关键词
neural nets; power transformer insulation; paper; transformer oil; polarisation; space charge; performance parameter calculation; trained artificial neural network; charging voltage; insulation response; nonlinearity; method performance parameters; polarisation current profile; voltage magnitude; time domain dielectric response; oil-paper insulation; polarisation-depolarisation current; specialised equipment; insulation conductivity; different charging voltages; FREQUENCY-DOMAIN; TRANSFORMER; SPECTROSCOPY; DIAGNOSIS; MOISTURE; PART;
D O I
10.1049/iet-smt.2018.5276
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Polarisation current profile varies non-linearly with a magnitude of charging voltage. This implies performance parameters obtained from polarisation-depolarisation current and those measured using specialised equipment cannot always be compared. Results reported in this study suggested that the non-linearity in insulation response can be explained in terms of the interaction between space charge and insulation conductivity. The influence of using different charging voltages and its effect on performance parameter calculation is investigated in this study with the help of laboratory samples. It is shown in this study that with the help of a trained artificial neural network, it is possible to identify the charging voltage at which insulation response exhibits minimum non-linearity. To test the accuracy of the proposed method performance parameters measured using commercial equipment are compared with those calculated from the polarisation current profile.
引用
收藏
页码:874 / 882
页数:9
相关论文
共 24 条
[1]   Temperature effects on the electrical conductivity of dielectric liquids [J].
Abedian, Behrouz ;
Baker, Kenneth N. .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2008, 15 (03) :888-892
[2]   CREATION OF CHARGE-CARRIERS IN NONPOLAR LIQUIDS [J].
ALJ, A ;
DENAT, A ;
GOSSE, JP ;
GOSSE, B ;
NAKAMURA, I .
IEEE TRANSACTIONS ON ELECTRICAL INSULATION, 1985, 20 (02) :221-231
[3]  
Ashkezari A.D., 2011, P IEEE PES INN SMART
[4]   Condition Assessment of Cellulosic Part in Power Transformer Insulation using Transfer Function Zero of Modified Debye Model [J].
Baral, A. ;
Chakravorti, S. .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2014, 21 (05) :2028-2036
[5]  
Bisht N., 2017, P CIGRE CBIP 6 INT C, P237
[6]  
Chakravorti S, 2013, POWER SYST, P1, DOI 10.1007/978-1-4471-5550-8
[7]   Moisture equilibrium in transformer paper-oil systems [J].
Du, Y ;
Zahn, M ;
Lesieutre, BC ;
Mamishev, AV ;
Lindgren, SR .
IEEE ELECTRICAL INSULATION MAGAZINE, 1999, 15 (01) :11-20
[8]  
Dutta Sourjya, 2016, 2016 European Conference on Networks and Communications (EuCNC), P1, DOI 10.1109/EuCNC.2016.7561016
[9]   Frequency response of oil impregnated pressboard and paper samples for estimating moisture in transformer insulation [J].
Ekanayake, Chandima ;
Gubanski, Stanislaw M. ;
Graczkowski, Andrzej ;
Walczak, Krzysztof .
IEEE TRANSACTIONS ON POWER DELIVERY, 2006, 21 (03) :1309-1317
[10]   On the Feasibility of Using Poles Computed from Frequency Domain Spectroscopy to Assess Oil Impregnated Paper Insulation Conditions [J].
Hadjadj, Yazid ;
Meghnefi, Fethi ;
Fofana, Issouf ;
Ezzaidi, Hassan .
ENERGIES, 2013, 6 (04) :2204-2220