An experimental study and 1-D analysis of an ejector with a movable primary nozzle that operates with R236fa

被引:15
作者
Chen, Shaojie [1 ]
Chen, Guangming [2 ]
Fang, Lingyun [1 ]
机构
[1] Zhejiang Univ, Inst Refrigerat & Cryogen, Hangzhou 310003, Zhejiang, Peoples R China
[2] Zhejiang Univ, Ningbo Inst Technol, Ningbo 315100, Zhejiang, Peoples R China
来源
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID | 2015年 / 60卷
基金
中国国家自然科学基金;
关键词
Ejector; Nozzle exit position; Choke; Refrigeration; REFRIGERATION SYSTEM; STEAM-EJECTOR;
D O I
10.1016/j.ijrefrig.2015.08.011
中图分类号
O414.1 [热力学];
学科分类号
摘要
The nozzle exit position is an important structural parameter of an ejector. Research shows that movable primary nozzle enhances performance of ejectors. The present work experimentally studied the critical entrainment ratios of an ejector at different nozzle positions, finding that the critical entrainment ratio first increases with the nozzle exit position and then remains constant. A 1-D model proposed to explain this phenomenon found that in a certain range, the critical entrainment ratio is determined by choking of the secondary flow in the converging cone. When the nozzle moves upstream, the mixed flow reaches sound speed at the constant area section, and the critical entrainment ratio remains unchanged. (C) 2015 Published by Elsevier Ltd.
引用
收藏
页码:19 / 25
页数:7
相关论文
共 20 条
[1]   Review on solar-driven ejector refrigeration technologies [J].
Abdulateef, J. M. ;
Sopian, K. ;
Alghoul, M. A. ;
Sulaiman, M. Y. .
RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2009, 13 (6-7) :1338-1349
[2]   Experimental investigation on the thermal stability of some new zero ODP refrigerants [J].
Angelino, G ;
Invernizzi, C .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2003, 26 (01) :51-58
[3]  
[Anonymous], 2014, ELECT J DIFFERENTIAL
[4]   A small capacity steam-ejector refrigerator: experimental investigation of a system using ejector with movable primary nozzle [J].
Aphornratana, S ;
Eames, IW .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 1997, 20 (05) :352-358
[5]   Experimental study on R-134a refrigeration system using a two-phase ejector as an expansion device [J].
Chaiwongsa, Praitoon ;
Wongwises, Somchai .
APPLIED THERMAL ENGINEERING, 2008, 28 (5-6) :467-477
[6]   Investigation of ejectors in refrigeration system: Optimum performance evaluation and ejector area ratios perspectives [J].
Chen, Jianyong ;
Havtun, Hans ;
Palm, Bjorn .
APPLIED THERMAL ENGINEERING, 2014, 64 (1-2) :182-191
[7]   Recent developments in ejector refrigeration technologies [J].
Chen, Xiangjie ;
Omer, Siddig ;
Worall, Mark ;
Riffat, Saffa .
RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2013, 19 :629-651
[8]   Ejectors: applications in refrigeration technology [J].
Chunnanond, K ;
Aphornratana, S .
RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2004, 8 (02) :129-155
[9]   An experimental investigation of a steam ejector refrigerator: the analysis of the pressure profile along the ejector [J].
Chunnanond, K ;
Aphornratana, S .
APPLIED THERMAL ENGINEERING, 2004, 24 (2-3) :311-322
[10]   A one dimensional model for the determination of an ejector entrainment ratio [J].
Garcia del Valle, Javier ;
Saiz Jabardo, Jose M. ;
Castro Ruiz, Francisco ;
Jose Alonso, Julio San .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2012, 35 (04) :772-784