Transient actions analysis of power transformers based on S-transform and hidden Markov model

被引:7
|
作者
Hasheminejad, S. [1 ]
Esmaeili, S. [1 ]
机构
[1] Shahid Bahonar Univ Kerman, Dept Elect Engn, Kerman 76169133, Iran
关键词
internal fault; magnetizing inrush current; transformer protection; S-transform; hidden Markov model; discrimination; MAGNETIZING INRUSH CURRENTS; WAVELET TRANSFORM; FAULTS; DISCRIMINATION; IDENTIFICATION; CLASSIFICATION; PROTECTION;
D O I
10.1002/etep.1740
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In this paper, the most important problem in the transformer relaying which is based on differential protection has been taken into consideration, and an effective solution has been proposed. When an internal fault occurs, as the differential current increases, relays should trip, but in the case of magnetizing inrush current which has almost the same amplitude as internal fault, it should stop wrong action. Hence, a method which can discriminate magnetizing inrush current from internal fault is required. Sometimes, when an external fault occurs, the magnitude of differential current can increase and leads to incorrect performance of differential relays. Therefore in the proposed method, discrimination of external fault from two former signal types is considered as well. The method proposed is based on the combination of S-transform and hidden Markov model (HMM). S-transform is used to extract some useful time-frequency information of the input signal, and then HMM is applied to classify signals by means of features extracted using S-transform. Classification process is performed in two different and independent routes (MAC and SDC routes). In the overall classification, results of both previous routes are considered to ensure this classification is very much reliable in different testing situations. Simulation process is performed by means of the combination of PSCAD/EMTDC and MATLAB software, and the effectiveness of the proposed technique has been verified with test cases. Copyright (C) 2013 John Wiley & Sons, Ltd.
引用
收藏
页码:826 / 841
页数:16
相关论文
共 50 条
  • [21] The Detection of Power Quality Disturbances Based on Generalized S-transform
    Liang, Chengbin
    Teng, Zhaosheng
    Li, Jianmin
    Liu, Fangxing
    He, Qing
    2020 CONFERENCE ON PRECISION ELECTROMAGNETIC MEASUREMENTS (CPEM), 2020,
  • [22] One Markov Model for Spare Analysis of Distribution Power Transformers
    Hamoud, Gomaa A.
    Yiu, Cynthia
    IEEE TRANSACTIONS ON POWER SYSTEMS, 2016, 31 (02) : 1643 - 1648
  • [23] Gait Analysis based on a Hidden Markov Model
    Bae, Joonbum
    2012 12TH INTERNATIONAL CONFERENCE ON CONTROL, AUTOMATION AND SYSTEMS (ICCAS), 2012, : 1025 - 1029
  • [24] Wavelet Analysis Based Hidden Markov Model
    Zhang, Xianyang
    Liu, Gang
    Flu, Chen
    Ma, Xiaolong
    PROCEEDINGS OF THE 38TH CHINESE CONTROL CONFERENCE (CCC), 2019, : 2913 - 2918
  • [25] Power Quality Analysis Using Modified S-Transform on ARM Processor
    Raj, Sandeep
    Phani, T. C. Krishna
    Dalei, Jyotirmayee
    2016 SIXTH INTERNATIONAL SYMPOSIUM ON EMBEDDED COMPUTING AND SYSTEM DESIGN (ISED 2016), 2016, : 166 - 170
  • [26] Power quality analysis using Discrete Orthogonal S-transform (DOST)
    Reddy, M. Jaya Bharata
    Raghupathy, Rama Krishnan
    Venkatesh, K. P.
    Mohanta, D. K.
    DIGITAL SIGNAL PROCESSING, 2013, 23 (02) : 616 - 626
  • [27] Simulation of Power Quality Using S-Transform
    Gu Jin-hong
    Liu Qi
    Cheng Chao-hui
    2010 INTERNATIONAL COLLOQUIUM ON COMPUTING, COMMUNICATION, CONTROL, AND MANAGEMENT (CCCM2010), VOL II, 2010, : 212 - 215
  • [28] Power Disturbances Classification Using S-Transform Based GA–PNN
    Manimala K.
    Selvi K.
    Journal of The Institution of Engineers (India): Series B, 2015, 96 (3) : 283 - 295
  • [29] Simulation of Power Quality Using S-Transform
    Gu Jin-hong
    Liu Qi
    Cheng Chao-hui
    MANUFACTURING SYSTEMS ENGINEERING, 2012, 429 : 172 - 178
  • [30] Continuous Wavelet Transform and Hidden Markov Model Based Target Detection
    Tugac, Serdar
    Efe, Murat
    RADIOENGINEERING, 2014, 23 (01) : 96 - 103