Desiccant-based AHU interacting with a CPVT collector: Simulation of energy and environmental performance

被引:44
作者
Calise, F. [1 ]
d'Accadia, M. Dentice [1 ]
Roselli, C. [2 ]
Sasso, M. [2 ]
Tariello, F. [2 ]
机构
[1] Univ Naples Federico II, DII, I-80125 Naples, Italy
[2] Univ Sannio, DING, I-82100 Benevento, Italy
关键词
Desiccant-based AHU; CPVT collector; Simulation; Solar cooling; Energy and environmental analysis; COOLING SYSTEM; SOLAR; DRIVEN; DEHUMIDIFICATION; DESIGN; CYCLE;
D O I
10.1016/j.solener.2013.11.001
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Desiccant-based Air Handling Units (AHU) provide significant technical and energy/environmental advantages with respect to conventional systems, especially when the regeneration of the desiccant material is obtained by means of a renewable energy source, such as solar energy. Such thermal energy may be provided by CPVT (Concentrating Photovoltaic/Thermal) collectors, simultaneously producing also electricity, which are considered one of the most promising solar technologies. In fact, CPVT thermal energy can drive (integrated by a natural-gas fired boiler) a desiccant-based AHU, since the silica-gel wheel, used for the dehumidification and included in that system, must be continuously regenerated. Here, the regeneration temperature of the wheel (40-70 degrees C, depending on the dehumidification required) is compatible with the CPVT outlet temperature (80-100 degrees C). Simultaneously, the electricity produced by CPVT collectors can feed the auxiliary devices of the plant. Furthermore, the heat supplied from the solar collector can be used for the pre and post heating of the process air during winter operation. A test facility in which a silica-gel desiccant wheel is included in a hybrid AHU has been located in Benevento (Southern Italy). In this paper, a desiccant-based AHU has been coupled with a novel CPVT, consisting of a parabolic trough concentrator and a linear triangular receiver. In order to analyze the system, a TRNSYS project based on models available in literature (some of them were calibrated and validated with experimental tests) has also been developed. Electricity produced by the CPVT collector is used to power the auxiliaries of the AHU, the chiller and also to balance the electric load of users, while thermal energy is used to heat the regeneration air flow during the summer period and the process air in the winter. Electricity in excess is sold to the grid, whereas the thermal energy in excess is used for production of domestic hot water (DHW). Eventual integrations of electricity and thermal energy are provided by the electric grid and by a gas-fired bolier, respectively. Energy and environmental performance of the overall system in terms of Primary Energy Saving and emission reduction with respect to a reference case are evaluated. The heat provided by the CPVT covers about 60% of thermal energy required by regeneration air and 30% of process air in winter operating mode. On an annual basis, the analyzed system obtains a Primary Energy Saving between 81% and 89%, depending on the DHW required. (C) 2013 Elsevier Ltd. All rights reserved.
引用
收藏
页码:574 / 594
页数:21
相关论文
共 74 条
  • [1] A high efficiency solar air conditioner using concentrating photovoltaic/thermal collectors
    Al-Alili, A.
    Hwang, Y.
    Radermacher, R.
    Kubo, I.
    [J]. APPLIED ENERGY, 2012, 93 : 138 - 147
  • [2] Distributed microtrigeneration systems
    Angrisani, G.
    Roselli, C.
    Sasso, M.
    [J]. PROGRESS IN ENERGY AND COMBUSTION SCIENCE, 2012, 38 (04) : 502 - 521
  • [3] Experimental analysis on the dehumidification and thermal performance of a desiccant wheel
    Angrisani, Giovanni
    Minichiello, Francesco
    Roselli, Carlo
    Sasso, Maurizio
    [J]. APPLIED ENERGY, 2012, 92 : 563 - 572
  • [4] Experimental validation of constant efficiency models for the subsystems of an unconventional desiccant-based Air Handling Unit and investigation of its performance
    Angrisani, Giovanni
    Roselli, Carlo
    Sasso, Maurizio
    [J]. APPLIED THERMAL ENGINEERING, 2012, 33-34 : 100 - 108
  • [5] Desiccant wheel regenerated by thermal energy from a microcogenerator: Experimental assessment of the performances
    Angrisani, Giovanni
    Capozzoli, Alfonso
    Minichiello, Francesco
    Roselli, Carlo
    Sasso, Maurizio
    [J]. APPLIED ENERGY, 2011, 88 (04) : 1354 - 1365
  • [6] Experimental investigation to optimise a desiccant HVAC system coupled to a small size cogenerator
    Angrisani, Giovanni
    Minichiello, Francesco
    Roselli, Carlo
    Sasso, Maurizio
    [J]. APPLIED THERMAL ENGINEERING, 2011, 31 (04) : 506 - 512
  • [7] [Anonymous], STAT PREV DAT STAT P
  • [8] [Anonymous], P EUR 2010 INT C SOL
  • [9] [Anonymous], 2010, TRNSYS 17: a TRaNsient SYstem Simulation program
  • [10] [Anonymous], P HEFAT 2011 8 INT C