On the Nature of Voltage Impasse Regions in Power System Dynamics Studies

被引:12
作者
Oluic, Marina [1 ]
Berggren, Bertil [2 ]
Echavarren, Francisco M. [3 ]
Ghandhari, Mehrdad [4 ]
Rouco, Luis [5 ]
机构
[1] KTH Royal Inst Technol, Elect Power & Energy Syst, S-10044 Stockholm, Sweden
[2] ABB Corp Res, S-72178 Vasteras, Sweden
[3] Comillas Pontificia Univ, Inst Res Technol, ICAI Sch Engn, Madrid 28015, Spain
[4] KTH Royal Inst Technol, S-10044 Stockholm, Sweden
[5] Univ Pontificia Comillas, Inst Invest Tecnol, Madrid 28015, Spain
关键词
Load models; power system dynamics; stability assessment; voltage collapse; voltage impasse region; STATE SECURITY MARGINS; SADDLE-NODE; STABILITY; COLLAPSE; BIFURCATIONS; TRANSIENT; OPTIMIZATION; COMPUTATION; FORMULATION; IMPROVEMENT;
D O I
10.1109/TPWRS.2017.2763123
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper presents a fundamental study of voltage collapses that occur on a post-fault trajectory of a stressed power system in seconds after large disturbances. The focus of the study are voltage collapses that are induced by certain load models. Using an n-machine-N-bus power system model, the paper explicitly shows that the voltage collapse is caused by the non-existence of a real, positive solution for a load voltage magnitude in different areas of a relative rotor angle space when the load is of non-linear type. These "areas without voltage solution" are denoted as Voltage Impasse Regions (VIR) and are mathematically characterized as trigonometric functions of (n-1) relative rotor angles. Once the post-fault trajectory enters a VIR, voltage magnitude solutions become complex or negative, the algebraic Jacobian becomes singular, and the behaviour of a system becomes undefined. The case study has been carried out using a simple 3-machine-1-load system with static load models. In the study, VIR appeared and enlarged as the non-linear (constant power and constant current) load increased. Furthermore, the non-convergence of time-domain solution occurred exactly at VIR, thereby confirming that the problem is of structural nature.
引用
收藏
页码:2660 / 2670
页数:11
相关论文
共 34 条
  • [1] [Anonymous], 1989, Energy Function Analysis for Power System Stability
  • [2] Equivalency of Continuation and Optimization Methods to Determine Saddle-Node and Limit-Induced Bifurcations in Power Systems
    Avalos, Rafael J.
    Canizares, Claudio A.
    Milano, Federico
    Conejo, Antonio J.
    [J]. IEEE TRANSACTIONS ON CIRCUITS AND SYSTEMS I-REGULAR PAPERS, 2009, 56 (01) : 210 - 223
  • [3] A Novel Online Load Shedding Strategy for Mitigating Fault-Induced Delayed Voltage Recovery
    Bai, Hua
    Ajjarapu, Venkataramana
    [J]. IEEE TRANSACTIONS ON POWER SYSTEMS, 2011, 26 (01) : 294 - 304
  • [4] ON THE NATURE OF UNSTABLE EQUILIBRIUM POINTS IN POWER-SYSTEMS
    BERGGREN, B
    ANDERSSON, G
    [J]. IEEE TRANSACTIONS ON POWER SYSTEMS, 1993, 8 (02) : 738 - 745
  • [5] Calculating optimal system parameters to maximize the distance to saddle-node bifurcations
    Canizares, CA
    [J]. IEEE TRANSACTIONS ON CIRCUITS AND SYSTEMS I-FUNDAMENTAL THEORY AND APPLICATIONS, 1998, 45 (03): : 225 - 237
  • [6] Canizares CA, 1996, IEEE T POWER SYST, V11, P1441, DOI 10.1109/59.535685
  • [7] ON VOLTAGE COLLAPSE IN ELECTRIC-POWER SYSTEMS
    CHIANG, HD
    DOBSON, I
    THOMAS, RJ
    THORP, JS
    FEKIHAHMED, L
    [J]. IEEE TRANSACTIONS ON POWER SYSTEMS, 1990, 5 (02) : 601 - 611
  • [8] Cutsem T.V., 1998, Voltage Stability of Electric Power Systems
  • [9] de Leon JAD, 2002, 2002 IEEE POWER ENGINEERING SOCIETY SUMMER MEETING, VOLS 1-3, CONFERENCE PROCEEDINGS, P745, DOI 10.1109/PESS.2002.1043412
  • [10] Formulation, computation and improvement of steady state security margins in power systems. Part II: Results
    Echavarren, F. M.
    Lobato, E.
    Rouco, L.
    Gomez, T.
    [J]. INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2011, 33 (02) : 347 - 358