Backflashover simulation of HV transmission lines with enhanced counterpoise groundings

被引:26
作者
Gatta, F. M. [1 ]
Geri, A. [1 ]
Lauria, S. [1 ]
Maccioni, M. [1 ]
机构
[1] Univ Roma La Sapienza, Dept Elect Engn, I-00184 Rome, Italy
关键词
Transmission line; Backflashover; Lightning; Tower groundings; Soil ionization; SOIL IONIZATION; LIGHTNING PERFORMANCE; TRANSIENT PERFORMANCE; DYNAMIC-MODEL; HIGH CURRENTS; SYSTEMS; ELECTRODES; BEHAVIOR; EMTP; PARAMETERS;
D O I
10.1016/j.epsr.2009.01.008
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper deals with the backflashover phenomenon in HV overhead transmission lines (TLs) with towers grounded by means of long counterpoises, typically used in high resistivity soils. Although long counterpoises are effective in reducing the grounding impedance at power frequency, their impulse response may affect negatively the TL backflashover rate. The study is focused on the enhancement of TL lightning performance obtainable by adding a small number of vertical grounding rods to horizontal counterpoises. An extensive ATP-EMTP parametric analysis, based on a detailed 161 kVTL model including the leader progression model (LPM) of line insulations and the non-linear transient behaviour of grounding systems, has been carried out taking into account several different values of soil resistivity as well as varying numbers, locations and lengths of additional vertical rods. Critical lightning current ranges causing backflashover have been then predicted for several lightning waveforms, of different severity. The paper shows that the addition of a few vertical grounding rods significantly improves TL lightning performance by increasing critical lightning current values. even if their influence is negligible at power frequency. The authors have ascertained an increment of average critical backflashover current up to similar to 55% for some typical TL grounding system configurations and lightning waveshapes. (C) 2009 Elsevier B.V. All rights reserved.
引用
收藏
页码:1076 / 1084
页数:9
相关论文
共 49 条
[1]  
Alternative Transients Programs, 1995, Rule Book
[2]   A method of a lightning surge analysis recommended in Japan using EMTP [J].
Ametani, A ;
Kawamura, T .
IEEE TRANSACTIONS ON POWER DELIVERY, 2005, 20 (02) :867-875
[3]  
[Anonymous], 2004, 600714 IEC TR
[4]  
Cattaneo S., 1992, P 21 EMTP US GROUP M
[5]  
CATTANEO S, 1994, P 29 U POW ENG C UPE, P538
[6]   Parameters of lightning strokes: A review [J].
Chowdhuri, P ;
Anderson, JG ;
Chisholm, WA ;
Field, TE ;
Ishii, M ;
Martinez, JA ;
Marz, MB ;
McDaniel, J ;
McDermott, TR ;
Mousa, AM ;
Narita, T ;
Nichols, DK ;
Short, TA .
IEEE TRANSACTIONS ON POWER DELIVERY, 2005, 20 (01) :346-358
[7]   Impulse impedance tests on laboratory model ground electrodes [J].
Chowdhuri, P .
IEE PROCEEDINGS-GENERATION TRANSMISSION AND DISTRIBUTION, 2003, 150 (04) :427-433
[8]   Nodal frequency analysis of grounding systems considering the soil ionization effect [J].
Cidrás, J ;
Otero, AF ;
Garrido, C .
IEEE TRANSACTIONS ON POWER DELIVERY, 2000, 15 (01) :103-107
[9]  
CIGRE Working Group 01 of SC 33, 1991, CIGRE BROCH, V64, P171
[10]  