Construction and Experimental Verification of Novel Online Partial Discharge Monitoring System Using Power Line Communication

被引:10
作者
Kakimoto, Yasutomo [1 ]
Yoshikawa, Hina [1 ]
Jogo, Tatsuki [1 ]
Wakisaka, Toshiyuki [1 ]
Kozako, Masahiro [1 ]
Hikita, Masayuki [1 ]
Sato, Hidefumi [2 ]
Tagashira, Hideki [3 ]
Soeda, Masahiro [4 ]
机构
[1] Kyushu Inst Technol, Tobata Ku, 1-1 Sensui Cho, Kitakyushu, Fukuoka, Japan
[2] Kyushu Elect Power Co Inc, Res & Dev Diagnost Tech, Fukuoka, Japan
[3] Kyushu Elect Power Co Inc, Res & Dev Commun Technol, Fukuoka, Japan
[4] Kyushu Elect Power Co Inc, Fukuoka, Japan
关键词
Partial discharges; Substations; Working environment noise; Power line communications; Attenuation; Monitoring; Signal resolution; power line communication; partial discharge (PD) detection; ferrite core;
D O I
10.1109/TDEI.2020.009081
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In this research, we aim to construct a completely new partial discharge (PD) monitoring system that applies inexpensive power line communication (PLC). We have proposed a PD detection method and monitoring system (PDMS-PLC) on the basis of PLC signal transfer rare is affected by an error due to disturbance. An attempt is made to identify PD source from the quadrant dependence of information transmission rate (hereinafter referred to PHY rate [Mbps]) by selecting a pair of quadrants of applied voltage phase; i.e. 1st and 3rd quadrants, or 2nd and 4th ones. It was found that the PHY (Abbreviation for the lowest physical layer in the OSI (open systems interconnection) hierarchical model.) rate number distribution reflects the PD characteristics obtained by the phase resolved PD (PRPD) pattern. Environmental noise level is also measured at an actual substation using PDMS-PLC. Consequently, the applicability of PDMS-PLC to PD signal detection and defect type identification is suggested.
引用
收藏
页码:2165 / 2171
页数:7
相关论文
共 11 条
[1]  
[Anonymous], 20105678772 IEEE
[2]  
Blokhintsev I., 2017, 2017 IEEE ELECT INSU, P1725
[3]  
Blokhintsev I, 2017, 2017 IEEE ELECTRICAL INSULATION CONFERENCE (EIC), P205, DOI 10.1109/EIC.2017.8004669
[4]  
Caprara A, 2018, 2018 IEEE ELECTRICAL INSULATION CONFERENCE (EIC), P495, DOI 10.1109/EIC.2018.8481094
[5]   A Hybrid Transformer PD Monitoring Method Using Simultaneous IEC60270 and RF Data [J].
Firuzi, Keyvan ;
Vakilian, Mehdi ;
Phung, B. Toan ;
Blackburn, Trevor R. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2019, 34 (04) :1374-1382
[6]  
Gao XZ, 2019, 2019 IEEE ELECTRICAL INSULATION CONFERENCE (EIC), P54, DOI [10.1109/eic43217.2019.9046569, 10.1109/EIC43217.2019.9046569]
[7]  
Sheng BJ, 2014, IEEE T DIELECT EL IN, V21, P948, DOI [10.1109/TDEI.2014.6832236, 10.1109/TDEI.2014.004228]
[8]   Novel Inductive Sensor Solutions for On-line Partial Discharge and Power Quality Monitoring [J].
Siddiqui, Bashir Ahmed ;
Pakonen, Pertti ;
Verho, Pekka .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2017, 24 (01) :209-216
[9]  
Yamashita K., 2019, ELECT INSULATION C E, P1144
[10]   Construction of Novel Online Partial Discharge Monitoring System in Model Power Apparatus Using Power Line Communication [J].
Yoshikawa, Hina ;
Masuda, Seiya ;
Kakimoto, Yasutomo ;
Puspitasari, Nuraida ;
Nakano, Yusuke ;
Kozako, Masahiro ;
Hikita, Masayuki ;
Sato, Hidefumi ;
Tagashira, Hideki ;
Ishida, Kazuhito .
PROCEEDINGS OF THE 21ST INTERNATIONAL SYMPOSIUM ON HIGH VOLTAGE ENGINEERING, VOL 1, 2020, 598 :635-642