The 40-Ω ground-fault phenomenon

被引:49
|
作者
Dagenhart, J [1 ]
机构
[1] Clapp Res Associates PC, Raleigh, NC 27612 USA
关键词
40-Omega ground-fault impedance; electrical distribution systems; minimum fault currents;
D O I
10.1109/28.821792
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
Coordination of protective de,ices on electrical distribution systems always involves the calculation of fault currents. These calculations almost always include a minimum fault current value. This minimum fault current value is not a bolted fault calculation; it includes an assumed impedance. Many utilities have assumed this impedance to be 40 Ohm. This paper examines that assumption and provides some guidance on this issue. This paper is based on a study sponsored by the Cooperative Research Network, a division of the National Rural Electric Cooperative Association, based in Arlington, VA. This original study was completed in 1997.
引用
收藏
页码:30 / 32
页数:3
相关论文
共 50 条
  • [31] Selective ground-fault protection based on active power of faulted components
    Mu, Long-Hua
    Meng, Qing-Hai
    Hu, Tian-Lu
    Zhongguo Kuangye Daxue Xuebao/Journal of China University of Mining & Technology, 2002, 31 (04): : 380 - 383
  • [32] The ground-fault circuit interrupter and its utility in the chemical laboratory.
    Li, RWC
    Gruber, J
    de Lucca, MA
    Lisboa, AS
    QUIMICA NOVA, 1998, 21 (03): : 341 - 342
  • [33] Investigation of ground-fault protection devices for photovoltaic power systems applications
    Bower, W
    Wiles, J
    CONFERENCE RECORD OF THE TWENTY-EIGHTH IEEE PHOTOVOLTAIC SPECIALISTS CONFERENCE - 2000, 2000, : 1378 - 1383
  • [34] GROUND-FAULT PROTECTION AND DETECTION FOR INDUSTRIAL AND COMMERCIAL DISTRIBUTION SYSTEMS.
    Regotti, A.A.
    Wargo, H.W.
    Westinghouse Engineer, 1974, 34 (03): : 80 - 83
  • [35] GRUBER HONORED, SHIPBOARD GROUND-FAULT DETECTORS DISCUSSED AT NY MET
    LEWANDOWSKI, EM
    MARINE TECHNOLOGY AND SNAME NEWS, 1995, 32 (03): : R24 - R24
  • [36] Fault analysis and simulation of ground-fault accident on transformer in 500 kV AC/DC grids
    Zhang, Bo
    Lu, Ping
    Kong, Jinjiao
    Liu, Rui
    Cao, Quanliang
    Shao, Hongbo
    Deng, Wanting
    Chen, Jun
    INTERNATIONAL JOURNAL OF APPLIED ELECTROMAGNETICS AND MECHANICS, 2019, 60 (01) : 1 - 12
  • [37] Ground-Fault Loop Impedance Calculations in Single-Phase Systems
    Liu, Haijun
    Mitolo, Massimo
    Qiu, Jun
    2013 49TH IEEE/IAS INDUSTRIAL & COMMERCIAL POWER SYSTEMS TECHNICAL CONF (I&CPS), 2013,
  • [38] Parametrization of ground-fault relays in MV distribution networks with resonant grounding
    Polajžer, Boštjan
    Pintarič, Matej
    Ribič, Janez
    Rošer, Miran
    Štumberger, Gorazd
    International Journal of Electrical Power and Energy Systems, 2022, 143
  • [39] Ground-fault fast transients in modern unit-connected generators
    Zielichowski, M
    Fulczyk, M
    Mydlikowski, R
    EUROPEAN TRANSACTIONS ON ELECTRICAL POWER, 2000, 10 (03): : 171 - 178
  • [40] Ground-fault feeder detection with fault-current and fault-resistance measurement in mine power systems
    Zeng, Xiangjun
    Li, K. K.
    Chan, W. L.
    Su, Sheng
    Wang, Yuanyuan
    IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2008, 44 (02) : 424 - 429