A case study on the air distribution in an operating room at Sarawak General Hospital Heart Centre (SGHHC) in Malaysia

被引:7
作者
Yau, Y. H. [1 ]
Ding, L. C. [1 ]
机构
[1] Univ Malaya, Dept Mech Engn, Kuala Lumpur 50603, Malaysia
关键词
Air distribution; Airflow; Computational fluid dynamics (CFD); Operating room; Malaysia; COMPUTATIONAL FLUID-DYNAMICS; VENTILATION PERFORMANCE; VELOCITY; THEATER;
D O I
10.1177/1420326X13499359
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
A fieldwork measurement and simulation studies were carried out at the operating room (OR)-5, Sarawak General Hospital Heart Centre (SGHHC). This hospital is located in East Malaysia and was commissioned in January 2011. The air condition at the inlets and several other locations in the room are measured for the validation of the computational fluid dynamics simulation. From the results, it is noted that the obstruction and heat dissipation effects from the surgical light should not be disregarded. The combination of both effects results in trapped heat in the region below the surgical light. Under the same total flow volume for the OR, it is observed that the OR with the uneven inlet velocities performs better than the OR with an even velocity distribution at the inlets. On the question of reducing the ventilation air consumption, it is proven that a reduction of air flow rate by 15% (to the average inlet air velocity of 0.3m/s) is possible in the OR.
引用
收藏
页码:1129 / 1141
页数:13
相关论文
共 13 条
[1]  
ANSYS, 2009, ANSYS WORKB US GUID
[2]   The integrated effect of medical lamp position and diffuser discharge velocity on ultra-clean ventilation performance in an operating theatre [J].
Chow, T. T. ;
Lin, Zhang ;
Bai, Wei .
INDOOR AND BUILT ENVIRONMENT, 2006, 15 (04) :315-331
[3]   Ventilation performance in the operating theatre against airborne infection: numerical study on an ultra-clean system [J].
Chow, TT ;
Yang, XY .
JOURNAL OF HOSPITAL INFECTION, 2005, 59 (02) :138-147
[4]   Computational fluid dynamics applications in hospital ventilation design [J].
Colquhoun, J ;
Partridge, L .
INDOOR AND BUILT ENVIRONMENT, 2003, 12 (1-2) :81-88
[5]   Air quality in operating theatres: the effect of waste anaesthetics on personnel and exposure prevention measures [J].
Dobrovolsky, L .
INDOOR AND BUILT ENVIRONMENT, 2003, 12 (1-2) :113-120
[6]   An investigation of air inlet velocity in simulating the dispersion of indoor contaminants via computational fluid dynamics [J].
Lee, E ;
Feigley, CE ;
Khan, J .
ANNALS OF OCCUPATIONAL HYGIENE, 2002, 46 (08) :701-712
[7]   Accuracy limitations for low-velocity measurements and draft assessment in rooms [J].
Melikov, Arsen K. ;
Popiolek, Z. ;
Silva, M. C. G. ;
Care, I. ;
Sefker, T. .
HVAC&R RESEARCH, 2007, 13 (06) :971-986
[8]  
Memarzadeh F., 2004, IAQ, P1
[9]  
Memarzadeh F., 2002, ASHRAE Transactions, V108, P3
[10]  
MOH, 2010, POL PROC INF CONTR