Mathematical modeling investigation on flow boiling and high efficiency heat dissipation of two rectangular radial microchannel heat exchangers

被引:17
作者
Song, Mengjie [1 ]
Jiang Zhengyong [1 ]
Dang Chaobin [2 ]
Jiang Yuyan [1 ]
Shen Jun [1 ]
Luo Xiaoyan [1 ]
机构
[1] Beijing Inst Technol, Sch Mech Engn, Dept Energy & Power Engn, Beijing 100081, Peoples R China
[2] Univ Fukui, Grad Sch Engn, 3-9-1 Bunkyo, Fukui, Fukui 9108507, Japan
基金
中国国家自然科学基金;
关键词
Microchannel heat exchanger; Radial structure; Mathematical modeling; Flow boiling; Heat transfer coefficient; Surface temperature; TRANSFER PERFORMANCE; PRESSURE-DROP; PREDICTION; SYSTEM; FLUID; WATER;
D O I
10.1016/j.ijheatmasstransfer.2022.122736
中图分类号
O414.1 [热力学];
学科分类号
摘要
To solve the heat dissipation problem of high heat flux devices, flow boiling heat transfer in microchannels is widely used and investigated. Two types of rectangular radial microchannel heat exchangers, without and with grooves, were experimentally studied and reported by us. To further improve their heat transfer performances by optimizing their structural parameters, two mathematical models are developed, with heat transfer coefficient (HTC) used as validation parameter. As analyzed, for two rectangular radial microchannel heat exchangers, without and with grooves, the average deviations are 3.62% and 7.03%, respectively. The modeling results show that, compared with the heat exchanger without grooves, the one with grooves always has better heat transfer performance. For two microchannel heat exchangers, without and with grooves, the influence of adjusting structure parameters on the HTC is obvious, and the maximum changes of HTC reaches 32.56 kW/m(2)K and 70.33 kW/m(2)K, respectively. Under a heating load of 400 W and a volume flow rate of 8 L/h, the heat transfer performance of heat exchanger without grooves could not be improved. While under the same conditions, the predicted HTC of the heat exchanger with grooves is improved to 102.56 kW/m2K, which is 58.69% higher than the experimental data. The results of this study are expected to provide references for the structural design optimization of microchannel heat exchangers. (C) 2022 Elsevier Ltd. All rights reserved.
引用
收藏
页数:17
相关论文
共 38 条
  • [31] Experimental investigation on the heat transfer characteristics of novel rectangle radial microchannel heat exchangers in two-phase flow cooling system for data centers
    Song Mengjie
    Dang Chaobin
    Eiji, Hihara
    [J]. JOURNAL OF THERMAL ANALYSIS AND CALORIMETRY, 2020, 141 (01) : 199 - 211
  • [32] HEAT-TRANSFER CORRELATIONS FOR NATURAL-CONVECTION BOILING
    STEPHAN, K
    ABDELSALAM, M
    [J]. INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 1980, 23 (01) : 73 - 87
  • [33] An experimental study on the heat transfer performance of a loop heat pipe system with ethanol-water mixture as working fluid for aircraft anti-icing
    Su Qian
    Chang Shinan
    Song Mengjie
    Zhao Yuanyuan
    Dang Chaobin
    [J]. INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2019, 139 : 280 - 292
  • [34] Heat transfer model for evaporation in microchannels. Part I: presentation of the model
    Thome, JR
    Dupont, V
    Jacobi, AM
    [J]. INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2004, 47 (14-16) : 3375 - 3385
  • [35] Experimental investigation of flow boiling characteristics in microchannels with the sinusoidal wavy sidewall
    Xia, G. D.
    Tang, Y. X.
    Zong, L. X.
    Ma, D. D.
    Jia, Y. T.
    Rong, R. Z.
    [J]. INTERNATIONAL COMMUNICATIONS IN HEAT AND MASS TRANSFER, 2019, 101 : 89 - 102
  • [36] Yadav A, 2021, CHEM ENG SCI, V31
  • [37] Development of a mechanistic model for sliding bubbles growth prediction in subcooled boiling flow
    Yoo, Junsoo
    Estrada-Perez, Carlos E.
    Hassan, Yassin A.
    [J]. APPLIED THERMAL ENGINEERING, 2018, 138 : 657 - 667
  • [38] Yoshida S., 1994, Trans. Jpn. Soc. Refrig. Air Cond. Eng, V11, P67