Performance of an unglazed transpire collector in the facade of a building for heating and cooling in combination with a desiccant evaporative cooler

被引:10
作者
Peci, F. [1 ]
Comino, F. [1 ]
Ruiz de Adana, M. [1 ]
机构
[1] Univ Cordoba, Escuela Politecn Super, Dept Quim Fis & Termodinam Aplicada, Antigua Carretera Nacl 4,Km 396, Cordoba 14072, Spain
关键词
Desiccant evaporative cooling; Unglazed solar collector; Ventilated facade; Building energy saving; Solar facade; AIR-CONDITIONING SYSTEM; NUMERICAL-ANALYSIS; SOLAR COLLECTORS; DRIVEN; OPTIMIZATION; WHEEL; OPERATION;
D O I
10.1016/j.renene.2018.01.029
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
Refurbishment of energy inefficient buildings is an effective way of reducing energy consumption in urban areas. This can be done by taking advantage of the renewable energy sources available, mainly, solar energy. Desiccant evaporative cooling combined with unglazed transpired collectors, UTC's, allows covering the heating demand in the cold season and cooling demand in the hot season. UTC's can be installed on the facades of buildings, meeting a double goal: refurbishing the building exterior and providing heating and cooling to indoor spaces. In this paper, a model of this system was implemented using TRNSYS and the energy savings obtained were evaluated in different climatic conditions, different facade orientations and different building shapes. The objective was to find the best conditions to install this system and estimating the energy savings that can be reached, and its costs. The results showed that the reduction of heating demand was possible in all climatic conditions, weakly depending on the shape and orientation of the UTC facade installed. Cooling was also possible, but it depended more on the shape of the building. The higher energy savings were found for the linear shape buildings. Therefore, refurbishment using a UTC facade could be an interesting alternative for energy saving throughout the year in these cases. (C) 2018 Elsevier Ltd. All rights reserved.
引用
收藏
页码:460 / 471
页数:12
相关论文
共 36 条
[1]   Evaluation and optimization of solar desiccant wheel performance [J].
Ahmed, MH ;
Kattab, NM ;
Fouad, M .
RENEWABLE ENERGY, 2005, 30 (03) :305-325
[2]   Performance analysis of an innovative small-scale trigeneration plant with liquid desiccant cooling system [J].
Badami, M. ;
Portoraro, A. .
ENERGY AND BUILDINGS, 2009, 41 (11) :1195-1204
[3]   Transpired solar collector installations in Wales and England [J].
Brown, Catherine ;
Perisoglou, Emmanouil ;
Hall, Richard ;
Stevenson, Vicki .
PROCEEDINGS OF THE 2ND INTERNATIONAL CONFERENCE ON SOLAR HEATING AND COOLING FOR BUILDINGS AND INDUSTRY (SHC 2013), 2014, 48 :18-27
[4]   Building integrated solar thermal collectors - A review [J].
Buker, Mahmut Sami ;
Riffat, Saffa B. .
RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2015, 51 :327-346
[5]   The optimization of the operation of a solar desiccant air handling unit coupled with a radiant floor [J].
Cejudo Lopez, Jose M. ;
Fernandez Hernandez, Francisco ;
Dominguez Munoz, Fernando ;
Carrillo Andres, Antonio .
ENERGY AND BUILDINGS, 2013, 62 :427-435
[6]   Experimental study of heat transfer and thermal performance with longitudinal fins of solar air heater [J].
Chabane, Foued ;
Moummi, Noureddine ;
Benramache, Said .
JOURNAL OF ADVANCED RESEARCH, 2014, 5 (02) :183-192
[7]  
Codigo Tecnico de la Edificacion (CTE), 2006, DOC BAS AH EN DB HE
[8]   Experimental and numerical analysis of desiccant wheels activated at low temperatures [J].
Comino, F. ;
Ruiz de Adana, M. .
ENERGY AND BUILDINGS, 2016, 133 :529-540
[9]   First and second order simplified models for the performance evaluation of low temperature activated desiccant wheels [J].
Comino, F. ;
Ruiz de Adana, M. ;
Peci, F. .
ENERGY AND BUILDINGS, 2016, 116 :574-582
[10]  
Duffle JA., 2006, Solar engineering of thermal processes, V3rd