Experimental study on the characteristics of non-steady state radiation heat transfer in the room with concrete ceiling radiant cooling panels

被引:24
作者
Zhang, Xuhan [1 ]
Li, Nianping [1 ]
Su, Lin [1 ]
Sun, Yeyao [1 ]
Qian, Jiawei [1 ]
机构
[1] Hunan Univ, Coll Civil Engn, Changsha 410082, Hunan, Peoples R China
基金
中国国家自然科学基金;
关键词
Concrete ceiling radiant cooling panels; Non-steady state; Radiation heat transfer; Start-up process; Indoor thermal environment; CAPACITY ESTIMATION MODEL; MIXED CONVECTION; SYSTEMS; PERFORMANCE; ENVIRONMENT; AIR;
D O I
10.1016/j.buildenv.2015.11.006
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
The dominant heat transfer between ceiling radiant cooling panels (CRCP) and indoor environment is the combined heat transfer of thermal radiation and natural convection. Currently, researchers usually discussed indoor radiation heat transfer under steady state conditions rather than non-steady state conditions. In this study, an experimental chamber was built to investigate the indoor parameter variations during the CRCP start-up process in summer, and a mathematical model was also established for further analysis of non-steady state radiation heat transfer. There was a concrete ceiling radiant cooling panel (C-CRCP) equipped in the chamber, and the panel was a concrete slab with pipes embedded in it. The experimental results showed that the temperature of the ceiling surface suddenly dropped after the C-CRCP started up, but the temperatures of the other inner surfaces and the indoor air decreased gradually with a similar trend. The radiant heat flux of the ceiling reached a trough rapidly, and then increased back to steady status step by step. Moreover, it took 7-9 h to nearly get steady status after the C-CRCP started up because of the thermal inertia and the thermal storage of concrete slab. The ratio of radiation heat transfer in the total heat transfer of the ceiling ranged from 40% to 60%. Based on the useful experimental data obtained in this C-CRCP system, a reliable start-up control strategy was also proposed in this paper. (C) 2015 Elsevier Ltd. All rights reserved.
引用
收藏
页码:157 / 169
页数:13
相关论文
共 39 条
[1]   Experimental study on the cooling capacity of a radiant cooled ceiling system [J].
Andres-Chicote, Manuel ;
Tejero-Gonzalez, Ana ;
Velasco-Gomez, Eloy ;
Javier Rey-Martinez, Francisco .
ENERGY AND BUILDINGS, 2012, 54 :207-214
[2]   Influence of the optical and geometrical properties of indoor environments for the thermal performances of chilled ceilings [J].
Arcuri, Natale ;
Bruno, Roberto ;
Bevilacqua, Piero .
ENERGY AND BUILDINGS, 2015, 88 :229-237
[3]   Proof of concept modeling of energy transfer mechanisms for radiant conditioning panels [J].
Ardehali, MM ;
Panah, NG ;
Smith, TF .
ENERGY CONVERSION AND MANAGEMENT, 2004, 45 (13-14) :2005-2017
[4]   Experimental evaluation of heat transfer coefficients between radiant ceiling and room [J].
Causone, Francesco ;
Corgnati, Stefano P. ;
Filippi, Marco ;
Olesen, Bjarne W. .
ENERGY AND BUILDINGS, 2009, 41 (06) :622-628
[5]   DIGITHON: A numerical model for the thermal balance of rooms equipped with radiant systems [J].
De Carli, Michele ;
Scarpa, Massimiliano ;
Tomasi, Roberta ;
Zarrella, Angelo .
BUILDING AND ENVIRONMENT, 2012, 57 :126-144
[6]  
Deng F., 2007, PRACTICAL HDB BUILDI
[7]   Testing and thermal modeling of radiant panels systems as commissioning tool [J].
Diaz, Nestor Fonseca ;
Cuevas, Cristian .
ENERGY CONVERSION AND MANAGEMENT, 2010, 51 (12) :2663-2677
[8]  
Ding Y., 2011, RES AIRFLOW PATTERNS
[9]   Optimal air-supply mode of hybrid system with radiant cooling and dedicated outdoor air [J].
Ding Yan ;
Tian Zhe ;
Zhu Neng .
JOURNAL OF CENTRAL SOUTH UNIVERSITY, 2015, 22 (02) :735-746
[10]   Experimental comparison of zone cooling load between radiant and air systems [J].
Feng, Jingjuan ;
Bauman, Fred ;
Schiavon, Stefano .
ENERGY AND BUILDINGS, 2014, 84 :152-159