Effect of High Voltage Impulses on Partial Discharge Characteristics of Oil-Impregnated Paper for Online Diagnostics

被引:0
|
作者
Nikjoo, Roya [1 ]
Taylor, Nathaniel [1 ]
Edin, Hans [1 ]
机构
[1] KTH Royal Inst Technol, Sch Elect Engn, Stockholm, Sweden
关键词
cavity discharge; surface discharge; PD pattern; oil-impregnated paper; superimposed impulse; LIGHTNING IMPULSE; INSULATION; TRANSFORMER; AC;
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The onset of Partial Discharge (PD) activity within an insulation system is often an important signature of degradation. Changes in the PD pattern aid assessment of the insulation degradation level. High voltage transients such as lightning and switching impulses are inevitable phenomena in power systems. They can impose electrical stresses on the insulation system of power components such as power transformers and their bushings which may lead to their failure. After the arrival of a transient the AC PD pattern may change, in a way that is influenced by the type of PD source. In this paper, the effect of HV impulses on the change of surface and cavity discharges of oil-impregnated paper has been investigated. With resemblance to the real situation, insulation samples have been subjected to an impulse voltage superimposed on the AC voltage. The behavior of PDs before and after the impulse for different defects and moisture content levels in oil-impregnated paper has been studied. The results show a distinctive behavior of PD due to the impulse for each defect and insulation condition, either by change in the PD rate and magnitude or by causing PD inception or extinction. Recording the voltage signals and associated PD measurements during and after the incident of high voltage transients can be used for assessing the insulation condition of power transformers and their bushings and interpretation of the recorded signals can be used for online diagnostics.
引用
收藏
页码:151 / 156
页数:6
相关论文
共 50 条
  • [41] Failure Characteristics and Mechanism of Nano-Modified Oil-Impregnated Paper Subjected to Repeated Impulse Voltage
    Sun, Potao
    Sima, Wenxia
    Zhang, Dingfei
    Jiang, Xiongwei
    Zhang, Huangjing
    Yin, Ze
    NANOMATERIALS, 2018, 8 (07):
  • [42] Partial discharge behaviour of oil impregnated paper bushings
    Colla, F
    Pompili, M
    Mazzetti, C
    Bartnikas, R
    CONFERENCE RECORD OF THE 1998 IEEE INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATION, VOLS 1 AND 2, 1998, : 35 - 38
  • [43] ELECTRICAL CHARACTERISTICS OF OIL-IMPREGNATED PAPER AS INSULATION FOR HV DC CABLES
    OCCHINI, E
    MASCHIO, G
    IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1967, PA86 (03): : 312 - &
  • [44] ELECTRICAL AGING OF OIL-IMPREGNATED HIGH-VOLTAGE DIELECTRICS
    GANGER, B
    MAIER, G
    IEEE TRANSACTIONS ON ELECTRICAL INSULATION, 1974, EI 9 (03): : 92 - 97
  • [45] Effects of Thermally Induced Bubbles on the Discharge Characteristics of Oil-Impregnated Pressboard
    Zhang, Rui
    Zhang, Qiaogen
    Guo, Chong
    Zhang, Zhetao
    Wu, Zhicheng
    Wen, Tao
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2022, 29 (03) : 1191 - 1199
  • [46] Fault development in wet, low voltage, oil-impregnated paper insulated cables
    Rowland, Simon M.
    Wang, Miao
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2008, 15 (02) : 484 - 491
  • [47] ANALYSIS OF VOLTAGE-TIME BREAKDOWN DATA FOR OIL-IMPREGNATED PAPER INSULATION
    WANG, M
    SRIVASTAVA, KD
    NEILSON, JB
    VANDERMAAR, AJ
    IEEE TRANSACTIONS ON ELECTRICAL INSULATION, 1991, 26 (04): : 837 - 839
  • [48] Aging of Oil-Impregnated Paper High Voltage Current Transformers: Long Duration Test and Lifespan Estimation
    Spressola, Flavio Eduardo
    Roman, Zoltan
    Oliveira, Rodrigo Gomes
    Lagos, Fernando Moreira
    Neto, Estacio Tavares Wanderley
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2024, 31 (01) : 358 - 365
  • [49] Aging of Oil-impregnated Transformer Insulation Studied through Partial Discharge Analysis
    Chen, X.
    Morshuis, P. H. F.
    Zhuang, Q.
    Smit, J. J.
    Xu, Z.
    PROCEEDINGS OF THE 2010 IEEE INTERNATIONAL CONFERENCE ON SOLID DIELECTRICS (ICSD 2010), 2010,
  • [50] Insulation Characteristics of Oil-impregnated Paper Bushing Under the Combined Electrical-thermal Effect
    Wang C.
    Hu W.
    Luo X.
    Xie X.
    Xu Z.
    Yin P.
    Gaodianya Jishu/High Voltage Engineering, 2019, 45 (08): : 2629 - 2636