An N-k Analytic Method of Composite Generation and Transmission with Interval Load

被引:8
作者
Hong, Shaoyun [1 ]
Cheng, Haozhong [1 ]
Zeng, Pingliang [2 ]
机构
[1] Shanghai Jiao Tong Univ, Dept Elect Engn, Shanghai 200240, Peoples R China
[2] Elect Power Res Inst China, Beijing 100192, Peoples R China
来源
ENERGIES | 2017年 / 10卷 / 02期
基金
中国国家自然科学基金;
关键词
mixed integer linear programming; interval load; the worst contingency of power system; minimum load shedding; transmission expansion planning; SECURITY ASSESSMENT; RISK-ASSESSMENT; POWER-SYSTEM; CONTINGENCIES; ALGORITHM; MODEL;
D O I
10.3390/en10020168
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
N-k contingency estimation plays a very important role in the operation and expansion planning of power systems, the method of which is traditionally based on heuristic screening. This paper stringently analyzes the best and worst states of power systems given the uncertainties of N-k contingency and interval load. For the sake of simplification and tractable computation, an approximate direct current (DC) power flow model was used. Rigorous optimization models were established for identifying the worst and best scenarios considering the contingencies of generators and transmission lines together with their uncertain loads. It is very useful to identify the worst N-k contingencies with interval loads. If the worst existing scenario meets security standards, all scenarios must satisfy it. The mathematical model established for finding the worst N-k contingency with interval load is a bi-level optimization model. In this paper, strong duality theory and mathematical linearization were applied to the solution of bi-level optimization. The computational results of standard cases validate the effectiveness of the proposed method and illustrate that generator contingency has more impact on minimum load shedding than transmission line contingency.
引用
收藏
页数:17
相关论文
共 25 条
  • [1] Enhanced multiobjective algorithm for transmission expansion planning considering N-1 security criterion
    Adrian Correa, Carlos
    Bolanos, Ricardo
    Garces, Alejandro
    [J]. INTERNATIONAL TRANSACTIONS ON ELECTRICAL ENERGY SYSTEMS, 2015, 25 (10): : 2225 - 2246
  • [2] [Anonymous], 1998, Practical bi-level optimization
  • [3] [Anonymous], 2005, Risk Assessment Of Power Systems: Models, Methods, and Applications
  • [4] Bilevel programming applied to power system vulnerability analysis under multiple contingencies
    Arroyo, J. M.
    [J]. IET GENERATION TRANSMISSION & DISTRIBUTION, 2010, 4 (02) : 178 - 190
  • [5] On the solution of the bilevel programming formulation of the terrorist threat problem
    Arroyo, JM
    Galiana, FD
    [J]. IEEE TRANSACTIONS ON POWER SYSTEMS, 2005, 20 (02) : 789 - 797
  • [6] Transmission and Wind Power Investment
    Baringo, Luis
    Conejo, Antonio J.
    [J]. IEEE TRANSACTIONS ON POWER SYSTEMS, 2012, 27 (02) : 885 - 893
  • [7] Contingency Ranking With Respect to Overloads in Very Large Power Systems Taking Into Account Uncertainty, Preventive, and Corrective Actions
    Fliscounakis, Stephane
    Panciatici, Patrick
    Capitanescu, Florin
    Wehenkel, Louis
    [J]. IEEE TRANSACTIONS ON POWER SYSTEMS, 2013, 28 (04) : 4909 - 4917
  • [8] Govind Singh J., 2014, INT T ELECT ENERGY S, DOI [10.1002/etep.1990, DOI 10.1002/ETEP.1990]
  • [9] An efficient scatter search algorithm to solve transmission expansion planning problem using a new load shedding index
    Habibi, M. R.
    Rashidinejad, M.
    Zeinaddini-Meymand, M.
    Fadainejad, R.
    [J]. INTERNATIONAL TRANSACTIONS ON ELECTRICAL ENERGY SYSTEMS, 2014, 24 (02): : 153 - 165
  • [10] N-k Induced Cascading Contingency Screening
    Jia, Youwei
    Meng, Ke
    Xu, Zhao
    [J]. IEEE TRANSACTIONS ON POWER SYSTEMS, 2015, 30 (05) : 2824 - 2825