摘要
The central heating technology with thermal storage technology is an important means to realize thermoelectric decoupling, meet heating demand, reduce primary energy consumption, and protect the ecological environment. For this paper, the numerical simulation method was used to study the temperature variation of large-capacity hot water storage tank (HWST) in an actual combined heat and power system. The influence of various factors, including the length diameter ratio, water supply temperature, and water supply flow, as well as the orifice diameter and number of the water distributor, on the flow uniformity and performance of the HWST was investigated. The results show that the heat storage efficiency and flow uniformity of the HWST can be improved by properly increasing the water supply flow, the orifice diameter, and number of the water distributor. Increasing the length diameter ratio can improve the flow uniformity, but it will reduce the heat storage efficiency of the HWST. Increasing the water supply temperature can increase heat storage efficiency of the HWST and accelerate the stratification of cold and hot water in the tank. Besides, the comprehensive analysis of the non-dimensional exergy loss calculation results, velocity field, and temperature field show that there is a certain coupling relationship between the non-dimensional exergy loss and flow uniformity at the initial stage of heat storage. In practical application, the influence of these factors on flow uniformity, heat storage efficiency, and non-dimensional exergy loss should be comprehensively considered in order to achieve the best heat storage and release performance of the HWST. This paper provides some engineering guidance for the application of large-capacity heat storage tanks in the combined heat and power (CHP) system.
引用
收藏
页数:14
相关论文
共 23 条
  • [1] CFD analysis of thermal stratification in domestic hot water storage tank during dynamic mode
    Abdelhak, Olfa
    Mhiri, Hatem
    Bournot, Philippe
    [J]. BUILDING SIMULATION, 2015, 8 (04) : 421 - 429
  • [2] Sustainable small-scale CHP technologies for buildings: the basis for multi-perspective decision-making
    Alanne, K
    Saari, A
    [J]. RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2004, 8 (05) : 401 - 431
  • [3] Andersen A.N., CHP PLANTS BIG THERM
  • [4] [Anonymous], 2005, GAS HEAT
  • [5] Constant flow rate charging characteristics of a full-scale stratified chilled water storage tank with double-ring slotted pipe diffusers
    Bahnfleth, WP
    Song, J
    [J]. APPLIED THERMAL ENGINEERING, 2005, 25 (17-18) : 3067 - 3082
  • [6] The effect of diffuser configuration on thermal stratification in a rectangular storage tank
    Chung, Jae Dong
    Cho, Sung Hwan
    Tae, Choon Seob
    Yoo, Hoseon
    [J]. RENEWABLE ENERGY, 2008, 33 (10) : 2236 - 2245
  • [7] Virtual prototyping of storage tanks by means of three-dimensional CFD and heat transfer numerical simulations
    Cònsul, R
    Rodríguez, I
    Pérez-Segarra, CD
    Soria, M
    [J]. SOLAR ENERGY, 2004, 77 (02) : 179 - 191
  • [8] Modeling of a thermal energy storage system based on coupled metal hydrides (magnesium iron - sodium alanate) for concentrating solar power plants
    d'Entremont, A.
    Corgnale, C.
    Sulic, M.
    Hardy, B.
    Zidan, R.
    Motyka, T.
    [J]. INTERNATIONAL JOURNAL OF HYDROGEN ENERGY, 2017, 42 (35) : 22518 - 22529
  • [9] Improved thermal stratification with obstacles placed inside the vertical mantled hot water tanks
    Erdemir, Dogan
    Altuntop, Necdet
    [J]. APPLIED THERMAL ENGINEERING, 2016, 100 : 20 - 29
  • [10] Experimental analysis of a domestic electric hot water storage tank.: Part II:: dynamic mode of operation
    Fernandez-Seara, Jose
    Uhia, Francisco J.
    Sieres, Jaime
    [J]. APPLIED THERMAL ENGINEERING, 2007, 27 (01) : 137 - 144