Influences of heat source forms on the cooling capacity of the radiant cooling terminal

被引:13
作者
Niu, Xiaolei [1 ]
Tian, Zhe [1 ]
Duan, Baodong [1 ]
Wang, Zhiqiang [2 ]
机构
[1] Tianjin Univ, MOE, Sch Environm Sci & Engn, Key Lab Efficient Utilizat Low & Medium Grade Ene, Tianjin 300072, Peoples R China
[2] Sci & Technol Engn Corp Ltd, IT Elect Eleventh Design & Res Inst, Dalian Branch, Dalian 116600, Peoples R China
关键词
Radiant cooling terminal; Heat source form; Heat transfer model; Cooling capacity; MIXED CONVECTION; THERMAL COMFORT; CEILING SYSTEMS; COOLED CEILINGS; PANEL CAPACITY; VENTILATION; ROOMS;
D O I
10.1016/j.enbuild.2013.12.013
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Heat source forms influence the cooling capacity of the radiant cooling terminal. This paper introduces three different forms of heat sources commonly used in the performance test of radiant cooling terminal: internal heat source, external heat source A and B. To external heat source A, the heat is supplied by one internal wall, while to external heat source B, the heat is supplied by four internal walls and the floor. Simulations of the cooling capacity of radiant cooling terminal under the conditions of different heat sources were conducted by establishing heat transfer models, respectively. The terminal cooling capacity under the conditions of external heat sources A and B can be enhanced by 10% and 13%, respectively, compared with that under the condition of internal heat source. The experimental research confirmed the accuracy of heat transfer models. Causes and influencing factors of terminal cooling performance discrepancy under the conditions of different heat sources were analyzed by using the heat transfer models. Through the analysis of the radiation proportion and the shape of the room under different heat sources, internal heat source is suggested in the testing of the terminal cooling performance. (C) 2013 Elsevier B.V. All rights reserved.
引用
收藏
页码:102 / 111
页数:10
相关论文
共 50 条
  • [1] Dehumidification-adjustable cooling of radiant cooling terminals based on a flat heat pipe
    Wu, Yifan
    Sun, Hongli
    Duan, Mengfan
    Lin, Borong
    Zhao, Hengxin
    BUILDING AND ENVIRONMENT, 2021, 194
  • [2] Heat transfer and cooling characteristics of concrete ceiling radiant cooling panel
    Su, Lin
    Li, Nianping
    Zhang, Xuhan
    Sun, Yeyao
    Qian, Jiawei
    APPLIED THERMAL ENGINEERING, 2015, 84 : 170 - 179
  • [3] Numerical analysis of temperature non-uniformity and cooling capacity for capillary ceiling radiant cooling panel
    Xie, Dong
    Wang, Yun
    Wang, Hanqing
    Mo, Shunquan
    Liao, Maili
    RENEWABLE ENERGY, 2016, 87 : 1154 - 1161
  • [4] Cooling capacity evaluation of ceiling radiant cooling panels using thermoelectric module
    Shin, Mi-Su
    Kim, Sang-Yeop
    Rhee, Kyu-Nam
    ENERGY AND BUILDINGS, 2024, 323
  • [5] Enhancement of cooling capacity through open-type installation of cooling radiant ceiling panel systems
    Shin, Mi Su
    Rhee, Kyu Nam
    Park, Sang Hoon
    Yeo, Myoung Souk
    Kim, Kwang Woo
    BUILDING AND ENVIRONMENT, 2019, 148 : 417 - 432
  • [6] EVALUATION OF THE RADIANT COOLING CEILING PANELS WITH A REVERSIBLE HEAT PUMP
    Rimar, Miroslav
    Fedak, Marcel
    Kulikov, Andrii
    Kulikova, Olha
    MM SCIENCE JOURNAL, 2021, 2021 : 5317 - 5321
  • [7] A Review of Studies on Heat Transfer in Buildings with Radiant Cooling Systems
    Hu, Rong
    Sun, Shilin
    Liang, Jincan
    Zhou, Zhiping
    Yin, Yingde
    BUILDINGS, 2023, 13 (08)
  • [8] Effect of acoustical clouds coverage and air movement on radiant chilled ceiling cooling capacity
    Karmann, Caroline
    Bauman, Fred
    Raftery, Paul
    Schiavon, Stefano
    Koupriyanov, Mike
    ENERGY AND BUILDINGS, 2018, 158 : 939 - 949
  • [9] Enhancing the cooling capacity of radiant ceiling panels by latent heat transfer of superhydrophobic surfaces
    Zhong, Ziwen
    Ma, Wei
    Yao, Shuhuai
    Xu, Xiangguo
    Niu, Jianlei
    ENERGY AND BUILDINGS, 2022, 263
  • [10] Practical cooling capacity estimation model for a suspended metal ceiling radiant cooling panel
    Jeong, Jae-Weon
    Mumma, Stanley A.
    BUILDING AND ENVIRONMENT, 2007, 42 (09) : 3176 - 3185