Assessing Insulating Oil Degradation by Means of Turbidity and UV/Vis Spectrophotometry Measurements

被引:76
|
作者
Hadjadj, Y. [1 ]
Fofana, I. [1 ]
Sabau, John [2 ]
Briosso, Eduardo [3 ]
机构
[1] Univ Quebec Chicoutimi, Canada Res Chair Insulating Liquids & Mixed Diele, Chicoutimi, PQ, Canada
[2] Insoil Canada Ltd, Calgary, AB T3A 4Y7, Canada
[3] CTM, Protect Relays Dept, Salto Grande, Uruguay
基金
加拿大自然科学与工程研究理事会;
关键词
Power transformer; insulation condition assessment; aging; oil; UV-spectrophotometry; turbidity; acidity; interfacial tension; dielectric dissipation factor; color;
D O I
10.1109/TDEI.2015.005111
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Oil is a vital part of the transformer body and (similarly to blood in a human being body) keeps responsibility for the condition of the entire organism. Oil is particularly responsible for functional serviceability of the entire insulation system. The insulating oil must be kept in pristine condition, since its condition can be a decisive factor, which determines the life span of the transformer. Fields and laboratory experiences have shown that transformer oil contains a vast amount of information. Oil analyses can be extremely useful in monitoring the condition of power transformers. To meet pressing needs of power industries, fast, inexpensive and reliable laboratory testing procedures are necessary. To ensure long-term reliability of oil filled power transformers, it is important to identify early sign of degradation of the insulating oil. In this paper, oil degradation was monitored with various ASTM test methods. Investigations were performed on service-aged oil samples as well as on oil samples aged in laboratory conditions. Many key parameters actually used to monitor the condition of transformer oil relative to oxidation/degradation were investigated. From the obtained results, correlations were found between some of them. The results indicate that Dissolved Decay Products (DDP) and turbidity, which change with a higher rate than interfacial tension (IFT) and Acid Number (AN) values, can be possibly used as an effective index for insulating oil degradation assessment. Limits are suggested which provide a "picture" of the fluid condition.
引用
收藏
页码:2653 / 2660
页数:8
相关论文
共 2 条
  • [1] UV-Vis Spectroscopy: A New Approach for Assessing the Color Index of Transformer Insulating Oil
    Leong, Yang Sing
    Ker, Pin Jern
    Jamaludin, M. Z.
    Nomanbhay, Saifuddin M.
    Ismail, Aiman
    Abdullah, Fairuz
    Looe, Hui Mun
    Lo, Chin Kim
    SENSORS, 2018, 18 (07)
  • [2] Effect of Oxidation of Aged Power Transformer Insulating Oil on UV-Vis Spectra
    Rashed, Abdellatif K.
    Mansour, Diaa-Eldin A.
    Rezk, A.
    Ghali, Mohsen
    2022 IEEE 21ST INTERNATIONAL CONFERENCE ON DIELECTRIC LIQUIDS (ICDL), 2022,