Experimental investigations of thermal managements solutions in data centers buildings for different arrangements of cold aisles containments

被引:88
作者
Nada, S. A. [1 ]
Elfeky, K. E. [1 ]
机构
[1] Benha Univ, Benha Fac Engn, Dept Mech Engn, Banha, Egypt
关键词
Data centers buildings; Thermal management; Physical modeling; Aisle containment; SYSTEMS;
D O I
10.1016/j.jobe.2015.11.001
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Cold aisles containments are used in data centers buildings to improve the thermal managements of the IT servers. In the present study, an experimental investigation of air flow and thermal management of data center buildings is conducted for different arrangements of cold aisles containments. A scaled physical model simulating real data centers is designed using scale modeling theory and constructed for the sake of the present experimental work. The data center scaled model accommodate a row of three racks; each rack included four servers for testing purposes. Three arrangements of cold aisles are tested: (i) free open cold aisle, (ii) semi-enclosed cold aisles where the aisles are enclosed from the sides, and (iii) full enclosed cold aisles, where the aisles are enclosed from sides and top. Front and rear racks temperatures profile, servers temperatures and performance measuring parameters Supply/Return Heat Index (SHI/RHI) are used to evaluate the thermal management/performance of the data centers racks. Experiments were conducted at different racks power densities. The results showed that (i) increasing data centers power density and supplied air flow rates improves SHI but increases servers temperature, (ii) using semi-enclosed cold aisles relatively improve the thermal performance of the data centers, (iii) using full enclosed cold aisles dramatically improve the thermal performance of the data center servers, and (vi) the percentage of enhancement in data centers performance due to using cold aisle containments dramatically increases with increasing the power density. (C) 2015 Elsevier Ltd. All rights reserved.
引用
收藏
页码:41 / 49
页数:9
相关论文
共 23 条
[1]  
[Anonymous], CISC VIS NETW IND GL
[2]  
[Anonymous], 2004, 99 TC AM SOC HEAT RE
[3]  
ASHRAE, 2008, ENV GUID DAT EQ
[4]   SCALE EFFECT IN ROOM AIR-FLOW STUDIES [J].
AWBI, HB ;
NEMRI, MM .
ENERGY AND BUILDINGS, 1990, 14 (03) :207-210
[5]   Evaluation of air management system's thermal performance for superior cooling efficiency in high-density data centers [J].
Cho, Jinkyun ;
Kim, Byungseon Sean .
ENERGY AND BUILDINGS, 2011, 43 (09) :2145-2155
[6]   Measurements and predictions of the air distribution systems in high compute density (Internet) data centers [J].
Cho, Jinkyun ;
Lim, Taesub ;
Kim, Byungseon Sean .
ENERGY AND BUILDINGS, 2009, 41 (10) :1107-1115
[7]  
Fernando H, 2012, INT CONF INF AUTOMAT, P273, DOI 10.1109/ICIAFS.2012.6419916
[8]  
Gondipalli S., 2008, P 11 IEEE ITHERM C O
[9]  
Herrlin M., 2006, P INT C THERM PHEN I
[10]  
Herrlin MK, 2006, P TEL EN C, P1