Thermal analysis of a cold room

被引:0
作者
La Fianza, G. [1 ]
Giametta, F. [1 ]
Brunetti, L. [1 ]
Orsino, M. [1 ]
Bianchi, B. [1 ]
Perone, C. [1 ]
Catalano, P. [1 ]
机构
[1] Univ Molise, Dept Agr Environm & Food, Campobasso, Italy
来源
VI INTERNATIONAL SYMPOSIUM ON APPLICATIONS OF MODELLING AS AN INNOVATIVE TECHNOLOGY IN THE HORTICULTURAL SUPPLY CHAIN MODEL-IT 2019 | 2021年 / 1311卷
关键词
freezing; convection; heat-transfer; cold room; vegetable products; COMPUTATIONAL FLUID-DYNAMICS; HEAT-TRANSFER; SIMULATION; DESIGN;
D O I
10.17660/ActaHortic.2021.1311.27
中图分类号
S2 [农业工程];
学科分类号
0828 ;
摘要
The purpose of this research was to study the storage of fresh raw horticultural material processed and frozen in an industrial plant in southern Italy. A simulation technique (validated by experimental tests) was used giving the chance to evaluate the effect of bins location on the cooling capacity of the cold room avoiding expensive experimental tests. An external cooling system and an intermediate fluid ensure the cooling of the products. The air is distributed inside the cold room by two blowers that provide the forced convection of the air itself. First of all, experimental tests were carried out to validate the preliminary results obtained from the previous experiment, and then the authors carried out a computational fluid dynamic (CFD) analysis in order to verify where a good arrangement of the storage bins is achieved inside the room. The tests were carried out in summer ( July) on zucchini and peppers. The important deviations in the temperature of the product are mainly due to the different position occupied by the bins in the room. In fact, they are positioned at different distances and heights from the forced convection fans. Both simulation and experimental results show that the raw material cooled in the shortest possible time was the one placed to the shortest distance from the wall and at the lowest height of the room because of the low heat transfer through the floor. By increasing the distance from the access door through which the most significant heat transfer takes place, there is a small variation due to the optimal position of the storage bins inside the room, which still allows a good distribution of air.
引用
收藏
页码:217 / 224
页数:8
相关论文
共 17 条
  • [1] Analysis of the effects of package design on the rate and uniformity of cooling of stacked pomegranates: Numerical and experimental studies
    Ambaw, A.
    Mukama, Matia
    Opara, U. L.
    [J]. COMPUTERS AND ELECTRONICS IN AGRICULTURE, 2017, 136 : 13 - 24
  • [2] The use of CFD to characterize and design post-harvest storage facilities: Past, present and future
    Ambaw, A.
    Delele, M. A.
    Defraeye, T.
    Ho, Q. T.
    Opara, L. U.
    Nicolai, B. M.
    Verboven, P.
    [J]. COMPUTERS AND ELECTRONICS IN AGRICULTURE, 2013, 93 : 184 - 194
  • [3] 3D computational fluid dynamics simulation and experimental validation for prediction of heat transfer in a new malaxer machine
    Ayr, Ubaldo
    Tamborrino, Antonia
    Catalano, Pasquale
    Bianchi, Biagio
    Leone, Alessandro
    [J]. JOURNAL OF FOOD ENGINEERING, 2015, 154 : 30 - 38
  • [4] Bianchi B, 2015, VET ITAL, V51, P85, DOI 10.12834/VetIt.689.5112.03
  • [5] Energetic analysis and optimal design of a CHP plant in a frozen food processing factory through a dynamical simulation model
    Catalano, Filippo
    Perone, Claudio
    Iannacci, Valentino
    Leone, Alessandro
    Tamborrino, Antonia
    Bianchi, Biagio
    [J]. ENERGY CONVERSION AND MANAGEMENT, 2020, 225
  • [6] Modified Atmosphere Packaging, Ultrasound and Chitosan: Effect of Co-Treatments on the Shelf-Life of Black Truffle (Tuber aestivum)
    Catalano, P.
    Tremonte, P.
    Reale, A.
    Tipaldi, L.
    Pannella, G.
    Di Renzo, T.
    Succi, M.
    La Fianza, G.
    Giametta, F.
    Sorrentino, E.
    [J]. XI INTERNATIONAL CONTROLLED AND MODIFIED ATMOSPHERE RESEARCH CONFERENCE, 2015, 1071 : 471 - 475
  • [7] Study of a prototype of an advanced mechanical ventilation system with heat recovery integrated by heat pump
    Fucci, F.
    Perone, C.
    La Fianza, G.
    Brunetti, L.
    Giametta, F.
    Catalano, P.
    [J]. ENERGY AND BUILDINGS, 2016, 133 : 111 - 121
  • [8] Guiqiang Wang, 2018, IOP Conference Series: Earth and Environmental Science, V189, DOI 10.1088/1755-1315/189/5/052065
  • [9] Hardenburg R.E., 1986, Agric. Handbook, V66, P47
  • [10] Preliminary study of airflow and heat transfer in a cold room filled with apple pallets: Comparison between two modelling approaches and experimental results
    Hoang, Hong-Minh
    Duret, Steven
    Flick, Denis
    Laguerre, Onrawee
    [J]. APPLIED THERMAL ENGINEERING, 2015, 76 : 367 - 381