Quartile Based Differential Protection of Power Transformer

被引:21
作者
Shah, Ashesh M. [1 ]
Bhalja, Bhavesh R. [2 ]
Patel, Rajesh M. [3 ]
Bhalja, Het [2 ]
Agarwal, Pramod [2 ]
Makwana, Yogesh M. [4 ]
Malik, Om P. [5 ]
机构
[1] Gujarat Technol Univ, Ahmadabad, Gujarat, India
[2] Indian Inst Technol Roorkee, Dept Elect Engn, Roorkee, Uttar Pradesh, India
[3] Marwadi Educ Fdn Grp Inst, Fac PG Studies & Res Engn & Technol, Rajkot, Gujarat, India
[4] Govt Engn Coll, Dept Elect Engn, Dahod, Gujarat, India
[5] Univ Calgary, Dept Elect & Comp Engn, Calgary, AB T2N 1N4, Canada
关键词
Surges; Power transformers; Windings; Current transformers; Circuit faults; Fault detection; Saturation magnetization; Power transformer; differential protection; fault detection ratio and quartile of superimposed differential currents; INRUSH CURRENT; FAULT-DIAGNOSIS; ALGORITHM; DISCRIMINATION; SATURATION; FREQUENCY; CURVE;
D O I
10.1109/TPWRD.2020.2968725
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
A new technique for power transformer protection, that depends on the calculation of fault detection ratio (FDR) based on quartile of superimposed differential currents is presented. Internal faults are detected by comparing FDR with the predetermined threshold derived through analytical analysis and verified based on simulation results. The performance of the presented scheme is tested by modeling an existing Indian power transmission network using PSCAD/EMTDC software. Various types of abnormal conditions such as magnetizing inrush (including sympathetic and recovery) and over-excitation along with several types of internal (winding, inter-winding and turn-to-turn) faults have been investigated. Its validity has also been checked on the data of magnetizing inrush and simultaneous inrush with the internal fault in the transformer, which was obtained from the real network. The results reveal the effectiveness of the suggested technique in differentiating internal faults from other abnormal conditions. Further, it remains stable during heavy through fault with current transformer saturation. It is equally applicable for different ratings and winding connections of power transformers. Finally, comparative evaluation of the proposed scheme with the conventional and several existing techniques shows its superiority in terms of higher sensitivity during internal faults and improved stability in case of non-internal faults.
引用
收藏
页码:2447 / 2458
页数:12
相关论文
共 43 条
[1]  
ABB, 2019, APPL MAN TRANSF PROT
[2]   Power transformer differential protection using current and voltage ratios [J].
Ali, E. ;
Helal, A. ;
Desouki, H. ;
Shebl, K. ;
Abdelkader, S. ;
Malik, O. P. .
ELECTRIC POWER SYSTEMS RESEARCH, 2018, 154 :140-150
[3]   Experimental results of ratios-based transformer differential protection scheme [J].
Ali, Elsaeed ;
Malik, Om P. ;
Abdelkader, Sobhy ;
Helal, Ahmed ;
Desouki, Hussein .
INTERNATIONAL TRANSACTIONS ON ELECTRICAL ENERGY SYSTEMS, 2019, 29 (11)
[4]  
[Anonymous], MAGNETISM
[5]  
[Anonymous], 2008, C37912008 IEEE, P1, DOI [DOI 10.1109/IEEESTD.2008.4639522, 10.1109/IEEESTD.2008.4483716]
[6]   Time-time-transform application to fault diagnosis of power transformers [J].
Ashrafian, A. ;
Vahidi, Behrooz ;
Mirsalim, Mojtaba .
IET GENERATION TRANSMISSION & DISTRIBUTION, 2014, 8 (06) :1156-1167
[7]   Power Transformer Differential Protection Based on Clarke's Transform and Fuzzy Systems [J].
Barbosa, Daniel ;
Chemin Netto, Ulisses ;
Coury, Denis V. ;
Oleskovicz, Mario .
IEEE TRANSACTIONS ON POWER DELIVERY, 2011, 26 (02) :1212-1220
[8]   A TRANSFORMER MODEL FOR WINDING FAULT STUDIES [J].
BASTARD, P ;
BERTRAND, P ;
MEUNIER, M .
IEEE TRANSACTIONS ON POWER DELIVERY, 1994, 9 (02) :690-699
[9]   A GDSC-Based Technique to Distinguish Transformer Magnetizing From Fault Currents [J].
Batista, Ygo Neto ;
de Souza, Helber Elias Paz ;
dos Santos Neves, Francisco de Assis ;
Dias Filho, Roberto Feliciano .
IEEE TRANSACTIONS ON POWER DELIVERY, 2018, 33 (02) :589-599
[10]  
Blackburn J.L., 2007, PROTECTIVE RELAYING, V3rd