Performance Evaluation of Centrifugal Refrigeration Compressor Using R1234yf and R1234ze(E) as Drop-In Replacements for R134a Refrigerant

被引:9
作者
Yi, Kexin [1 ]
Zhao, Yuanyang [1 ]
Liu, Guangbin [1 ]
Yang, Qichao [1 ]
Yu, Guoxin [2 ]
Li, Liansheng [1 ]
机构
[1] Qingdao Univ Sci & Technol, Coll Electromech Engn, Dept Proc Control & Equipment Engn, Qingdao 260061, Peoples R China
[2] Qingdao Haier Smart Technol R&D Co Ltd, Qingdao 266103, Peoples R China
关键词
centrifugal compressor; chiller; refrigerant; R1234yf; R1234ze(E); R134a; BOILING HEAT-TRANSFER; PRESSURE-DROP; CONDENSATION; HFO-1234YF; HFC-134A; SYSTEM;
D O I
10.3390/en15072552
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
With the increasing global requirements for environmental protection, refrigerants with ODP of 0 and low GWP are widely concerned and applied. In this paper, the CFD numerical method simulates the R134a centrifugal compressor directly replaced by R1234yf and R1234ze(E). The results show that at the same compressor rotational speed, using R1234yf to replace R134a directly can obtain a higher cooling capacity, but it reduces COP by about 12.5%; using R1234ze(E) to replace R134a directly reduces the cooling capacity under partial working conditions, the COP is reduced by about 7.0%. When the evaporation temperature, condensation temperature, and cooling capacity are the same, compared with the R134a unit, the COP of the R1234ze(E) unit is reduced by about 5.14%, and it is reduced by about 8.93% for the R1234yf unit. For the R134a centrifugal chiller, the drop-in replacement of R134a with R1234ze(E) can obtain better system performance compared with R1234yf.
引用
收藏
页数:17
相关论文
共 31 条
  • [1] [Anonymous], 2016, 128432016 JBT MIN IN
  • [2] Performance evaluation of an automotive air conditioning and heat pump system using R1234yf and R134a
    Aral, Mumin Celil
    Suhermanto, Mukhamad
    Hosoz, Murat
    [J]. SCIENCE AND TECHNOLOGY FOR THE BUILT ENVIRONMENT, 2021, 27 (01) : 44 - 60
  • [3] Investigation of new generation refrigerants under two different ejector mixing theories
    Atmaca, Ayse Ugurcan
    Erek, Aytunc
    Ekren, Orhan
    [J]. 4TH INTERNATIONAL CONFERENCE ON ENERGY AND ENVIRONMENT RESEARCH, ICEER 2017, 2017, 136 : 394 - 401
  • [4] Analysis of environmentally friendly refrigerant options for window air conditioners
    Bansal, Pradeep
    Shen, Bo
    [J]. SCIENCE AND TECHNOLOGY FOR THE BUILT ENVIRONMENT, 2015, 21 (05) : 483 - 490
  • [5] Experimental assessment of alternative low global warming potential refrigerants for automotive air conditioners application
    Chen, Xinwen
    Liang, Kun
    Li, Zhaohua
    Zhao, Yi
    Xu, Jing
    Jiang, Hanying
    [J]. CASE STUDIES IN THERMAL ENGINEERING, 2020, 22
  • [6] Thermo-economic and environmental analysis of a small capacity vapor compression refrigeration system using R290, R1234yf, and R600a
    de Paula, Cleison Henrique
    Duarte, Willian Moreira
    Martins Rocha, Thiago Torres
    de Oliveira, Raphael Nunes
    Mendes, Ramon de Paoli
    Torres Maia, Antonio Augusto
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION, 2020, 118 : 250 - 260
  • [7] CFD Based Design for Ejector Cooling System Using HFOS (1234ze(E) and 1234yf)
    Elbarghthi, Anas F. A.
    Mohamed, Saleh
    Nguyen, Van Vu
    Dvorak, Vaclav
    [J]. ENERGIES, 2020, 13 (06)
  • [8] Thermodynamic and heat transfer analyses for R1234yf and R1234ze(E) as drop-in replacements for R134a in a small power refrigerating system
    Jankovic, Zvonimir
    Sieres Atienza, Jaime
    Martinez Suarez, Jose Antonio
    [J]. APPLIED THERMAL ENGINEERING, 2015, 80 : 42 - 54
  • [9] Study on activated carbon/HFO-1234ze(E) based adsorption cooling cycle
    Jribi, Skander
    Saha, Bidyut Baran
    Koyama, Shigeru
    Chakraborty, Anutosh
    Ng, Kim Choon
    [J]. APPLIED THERMAL ENGINEERING, 2013, 50 (02) : 1570 - 1575
  • [10] A brief performance comparison of R1234yf and R134a in a bench tester for automobile applications
    Lee, Yohan
    Jung, Dongsoo
    [J]. APPLIED THERMAL ENGINEERING, 2012, 35 : 240 - 242