Studies on the performance of a CO2 air conditioning system using an ejector as an expansion device

被引:41
作者
Lee, Jae Seung [1 ]
Kim, Mo Se [2 ]
Kim, Min Soo [2 ]
机构
[1] Korea Dist Heating Corp, R&D Inst, CHP & DH Technol Team, Seoul 135220, South Korea
[2] Seoul Natl Univ, Sch Mech & Aerosp Engn, Div WCU Multiscale Mech Design, Seoul 151744, South Korea
来源
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID | 2014年 / 38卷
关键词
Carbon dioxide; Performance; Ejector; Air conditioning; REFRIGERATION CYCLE;
D O I
10.1016/j.ijrefrig.2013.08.019
中图分类号
O414.1 [热力学];
学科分类号
摘要
Environmental issues such as stratospheric ozone depletion and global warming have been the primary motivations for recent research in the air-conditioning and refrigeration fields. The CO2 air-conditioning system forms a transcritical cycle which shows slightly degraded performance compared to the conventional system. To overcome this disadvantage, a cycle adopting an ejector is suggested. Experimental results of a CO2 air-conditioning system using an ejector were compared for various outdoor temperatures and inverter frequencies. The COPs of an air-conditioning system using an ejector and conventional system were calculated and compared based on the pressures and temperatures of experiments. The cooling capacity and COP in the air-conditioning system using an ejector are higher than those in the conventional system at an entrainment ratio greater than 0.76. In addition, better performance is shown at entrainment ratio greater than a certain value in other test conditions. (C) 2013 Elsevier Ltd and IIR. All rights reserved.
引用
收藏
页码:140 / 152
页数:13
相关论文
共 26 条
[1]  
[Anonymous], 2002, INT J AIR-COND REFRI
[2]   Modelling and optimization of two-phase ejectors for cooling systems [J].
Cizungu, K ;
Groll, M ;
Ling, ZG .
APPLIED THERMAL ENGINEERING, 2005, 25 (13) :1979-1994
[3]   Experimental investigation on the performance of the refrigeration cycle using a two-phase ejector as an expansion device [J].
Disawas, S ;
Wongwises, S .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2004, 27 (06) :587-594
[4]  
Domanski P.A., 1995, THEORETICAL EVALUATI
[5]   Experimental validation of a prototype ejector designed to reduce throttling losses encountered in transcritical R744 system operation [J].
Elbel, Stefan ;
Hrnjak, Pega .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2008, 31 (03) :411-422
[6]  
Gay N. J., 1931, U.S. Patent, Patent No. [1,836,318, 186318]
[7]  
Kemper G.A., 1996, U.S. Patent, Patent No. [3,277,660, 3277660]
[8]  
Kim Mo Se, 2009, International Journal of Air-Conditioning and Refrigeration, V17, P100
[9]  
Korea Standard Associations, 2002, KS C 9306 AIR COND
[10]  
Kornhauser A.A., 1990, P 1990 USNCRIIR PURD, P10