Failure analysis of copper tube used in a refrigerating plant

被引:35
|
作者
Chandra, K. [1 ]
Kain, Vivekanand [1 ]
Shetty, P. S. [2 ]
Kishan, Ram [2 ]
机构
[1] Bhabha Atom Res Ctr, Div Mat Sci, Mumbai 400085, Maharashtra, India
[2] Bhabha Atom Res Ctr, Tech Serv Div, Mumbai 400085, Maharashtra, India
关键词
Copper; Failure analysis; Formicary corrosion; Ant-nest corrosion; Cracking; ANT-NEST CORROSION; LOCALIZED CORROSION;
D O I
10.1016/j.engfailanal.2013.11.014
中图分类号
TH [机械、仪表工业];
学科分类号
0802 ;
摘要
This paper reports the failure analysis of a leaked copper tube used in a refrigerating plant for carrying polyol ester oil for lubrication and cooling of compressor bearings. Failure had occurred at the bent region of the tube in the form of a wide diametric crack. The crack was intergranular and filled with corrosion products. The failed region on the inner diameter side of the tube had red-brown and dull-black surface films which were identified as cuprous oxide. No degradation or decomposition of the lubricant oil was detected. The microscopic examination of the cross-section of the tube showed corrosion degradation on both the outer and inner diameter surfaces with similar morphology. The corrosion morphology consisted of pit tunnels with fine longitudinal cracks bridging individual pitted regions typical of ant-nest corrosion. A few cracks, at the bent region of the tube, had originated through the pits and propagated along the wall thickness. The failure was concluded to be due to ant-nest corrosion of copper in the presence of carboxylic acid. Organic compounds used during the fabrication and joining of the copper tubes, if not properly cleaned, may decompose to carboxylic acid in presence of air and moisture. (C) 2013 Elsevier Ltd. All rights reserved.
引用
收藏
页码:1 / 11
页数:11
相关论文
共 50 条
  • [41] Failure analysis of a railway copper contact strip
    Azevedo, CRF
    Sinatora, A
    ENGINEERING FAILURE ANALYSIS, 2004, 11 (06) : 829 - 841
  • [42] Failure analysis of carbon steel pipes used for underground condensate pipeline in the power station
    Lee, Jongmin
    Han, Shinho
    Kim, Kyoungmun
    Kim, Heongkee
    Lee, Ungi
    ENGINEERING FAILURE ANALYSIS, 2013, 34 : 300 - 307
  • [43] Failure analysis used for remanufacturing of steel rolling components
    Hai-dou Wang
    Bin-shi Xu
    Shi-cheng Wei
    Xian-cheng Zhang
    Guo Jin
    Yi Jiang
    Journal of Central South University of Technology, 2005, 12 : 30 - 33
  • [44] Failure analysis used for remanufacturing of steel rolling components
    王海斗
    徐滨士
    魏世丞
    张显程
    金国
    姜祎
    Journal of Central South University, 2005, (S2) : 30 - 33
  • [45] Failure analysis used for remanufacturing of steel rolling components
    Wang, HD
    Xu, BS
    Wei, SC
    Zhang, XC
    Jin, G
    Jiang, Y
    JOURNAL OF CENTRAL SOUTH UNIVERSITY OF TECHNOLOGY, 2005, 12 (2): : 30 - 33
  • [46] Failure Analysis of Steady Clamps Used in Electrified Railway
    Chu Q.
    Zhang M.
    Chen Y.
    Journal of Failure Analysis and Prevention, 2014, 14 (05) : 588 - 593
  • [47] Failure analysis of NiTi wires used in medical applications
    James B.
    Foulds J.
    Eiselstein L.
    Journal of Failure Analysis and Prevention, 2005, 5 (5) : 82 - 87
  • [48] Failure analysis of a sleeper anchor model used in railroads
    de Faria, Geraldo Lucio
    Godefroid, Leonardo Barbosa
    Candido, Luiz Claudio
    de Souza Santos, Diego Antonio
    ENGINEERING FAILURE ANALYSIS, 2017, 79 : 565 - 574
  • [49] Failure analysis of power plant boiler material
    Ai J.H.
    Lin H.Y.
    Qi Y.X.
    Journal of Failure Analysis and Prevention, 2004, 4 (2) : 73 - 77
  • [50] Failure analysis of welded 0Cr13Al tube bundle in a heat exchanger
    Guo, C.
    Han, C. J.
    Tang, Y. M.
    Zuo, Y.
    Lin, S. Z.
    ENGINEERING FAILURE ANALYSIS, 2011, 18 (03) : 890 - 894