Failure analysis of copper tube used in a refrigerating plant

被引:39
作者
Chandra, K. [1 ]
Kain, Vivekanand [1 ]
Shetty, P. S. [2 ]
Kishan, Ram [2 ]
机构
[1] Bhabha Atom Res Ctr, Div Mat Sci, Mumbai 400085, Maharashtra, India
[2] Bhabha Atom Res Ctr, Tech Serv Div, Mumbai 400085, Maharashtra, India
关键词
Copper; Failure analysis; Formicary corrosion; Ant-nest corrosion; Cracking; ANT-NEST CORROSION; LOCALIZED CORROSION;
D O I
10.1016/j.engfailanal.2013.11.014
中图分类号
TH [机械、仪表工业];
学科分类号
0802 ;
摘要
This paper reports the failure analysis of a leaked copper tube used in a refrigerating plant for carrying polyol ester oil for lubrication and cooling of compressor bearings. Failure had occurred at the bent region of the tube in the form of a wide diametric crack. The crack was intergranular and filled with corrosion products. The failed region on the inner diameter side of the tube had red-brown and dull-black surface films which were identified as cuprous oxide. No degradation or decomposition of the lubricant oil was detected. The microscopic examination of the cross-section of the tube showed corrosion degradation on both the outer and inner diameter surfaces with similar morphology. The corrosion morphology consisted of pit tunnels with fine longitudinal cracks bridging individual pitted regions typical of ant-nest corrosion. A few cracks, at the bent region of the tube, had originated through the pits and propagated along the wall thickness. The failure was concluded to be due to ant-nest corrosion of copper in the presence of carboxylic acid. Organic compounds used during the fabrication and joining of the copper tubes, if not properly cleaned, may decompose to carboxylic acid in presence of air and moisture. (C) 2013 Elsevier Ltd. All rights reserved.
引用
收藏
页码:1 / 11
页数:11
相关论文
共 14 条
[1]  
[Anonymous], ANN BOOK ASTM STAND
[2]   Kinetic Study of Formate Compounds Developed on Copper in the Presence of Formic Acid Vapor [J].
Bastidas, D. M. ;
La Iglesia, V. M. ;
Cano, E. ;
Fajardo, S. ;
Bastidas, J. M. .
JOURNAL OF THE ELECTROCHEMICAL SOCIETY, 2008, 155 (12) :C578-C582
[3]  
Bastidas DM, 2006, REV METAL MADRID, V42, P367
[4]   Copper deterioration: causes, diagnosis and risk minimisation [J].
Bastidas, D. M. ;
Criado, M. ;
Fajardo, S. ;
La Iglesia, V. M. ;
Cano, E. ;
Bastidas, J. M. .
INTERNATIONAL MATERIALS REVIEWS, 2010, 55 (02) :99-127
[5]  
Corbett RA, ANT NEST CORROSION D, P1
[6]   Air Conditioner Failure Investigation-Intergranular Cracking in a Pure Copper Condenser Tube [J].
Duffner, D. H. .
JOURNAL OF FAILURE ANALYSIS AND PREVENTION, 2005, 5 (01) :79-85
[7]  
EDWARDS JO, 1977, MATER PERFORMANCE, V16, P18
[8]  
Elliott P, ANT NEST CORROSION E, P1
[9]   Stress-Corrosion Cracking in Copper Refrigerant Tubing [J].
McDougal, J. L. ;
Stevenson, M. E. .
JOURNAL OF FAILURE ANALYSIS AND PREVENTION, 2005, 5 (01) :13-17
[10]   A microstructural aspect of intergranular stress corrosion cracking of semi-hard U-bend tubes of commercially pure copper in cooling systems [J].
Miyamoto, H. ;
Saburi, D. ;
Fujiwara, H. .
ENGINEERING FAILURE ANALYSIS, 2012, 26 :108-119