Variation of Discharge Characteristics With Temperature in Moving Transformer Oil Contaminated by Metallic Particles

被引:26
作者
Pan, Cheng [1 ]
Tang, Ju [1 ,2 ]
Zhang, Yongze [2 ]
Luo, Xinyu [2 ]
Li, Xingxing [2 ]
机构
[1] Wuhan Univ, Sch Elect Engn, Wuhan 430072, Hubei, Peoples R China
[2] Chongqing Univ, State Key Lab Power Transmiss Equipment & Syst Se, Chongqing 400044, Peoples R China
基金
中国博士后科学基金; 中国国家自然科学基金;
关键词
Temperature; partial discharge; breakdown; moving transformer oil; metallic particles; INSULATING OIL; COMBINED AC; DC; BREAKDOWN; BEHAVIOR;
D O I
10.1109/ACCESS.2018.2856580
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
During the operation of power transformers, the insulating oil is actually in a moving state due to the effects of various cooling systems. Therefore, the investigation on insulation characters of moving transformer oil is necessary. In this paper, the influences of temperature on partial discharge (PD) and breakdown characteristics of moving transformer oil contaminated by metallic particles were experimentally studied at first. It was found that the PD magnitude and frequency first decreased and then became higher when the temperature increased from 40 degrees C to 80 degrees C, and a minimum point appeared between 70 degrees C and 80 degrees C. On the contrary, the dependence of breakdown voltage on temperature showed an opposite tendency. In order to explain the experimental results, a simulation model involving multiple forces was constructed to obtain the movement trajectory of particles. The increase of oil temperature leaded to the decrease of dynamic viscosity of transformer oil, so the forces acting on particles and their movement characters changed. As the temperature increased, the collision frequency between particles and electrodes first decreased and then became higher, and there was a minimum point between 70 degrees C and 80 degrees C. This changing tendency was in accordance with the dependence of PD parameters on the oil temperature. In terms of the above results, the effects of temperature on PD frequency and breakdown voltage were discussed.
引用
收藏
页码:40050 / 40058
页数:9
相关论文
共 24 条
[1]  
[Anonymous], TECH REP
[2]  
[Anonymous], P 3 INT C EL POW EN
[3]   MICRO-DISCHARGES FROM PARTICLES IN TRANSFORMER OIL [J].
BIRLASEKARAN, S ;
DARVENIZA, M .
IEEE TRANSACTIONS ON ELECTRICAL INSULATION, 1976, 11 (04) :162-163
[4]   Particle-initiated breakdown in a quasi-uniform field in transformer oil [J].
Carraz, F ;
Rain, P ;
Tobazeon, R .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 1995, 2 (06) :1052-1063
[5]  
CIGRE, 2000, Technical Brochure 443
[6]  
Danikas M. G., 1990, IEEE Electrical Insulation Magazine, V6, P27, DOI 10.1109/57.63080
[7]   Modeling of conductive particle behavior in insulating fluids affected by DC electric fields [J].
Dascalescu, L ;
Mihailescu, M ;
Tobazeon, R .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1998, 34 (01) :66-74
[8]  
Jan ST, 2015, INT C DAT MIN CIV ME, P49
[9]  
JAYARAM S, 1993, IEEE 1993 ANNUAL REPORT, P396, DOI 10.1109/CEIDP.1993.378940
[10]   Partial-Discharge Characteristics of Free Spherical Conducting Particles Under AC Condition in Transformer Oils [J].
Li, Junhao ;
Hu, Quanwei ;
Zhao, Xuefeng ;
Yao, Xiu ;
Luo, Yongfen ;
Li, Yanming .
IEEE TRANSACTIONS ON POWER DELIVERY, 2011, 26 (02) :538-546