Energy and exergy analysis of a double effect absorption refrigeration system based on different heat sources

被引:82
|
作者
Kaynakli, Omer [1 ]
Saka, Kenan [2 ]
Kaynakli, Faruk [3 ]
机构
[1] Uludag Univ, Fac Engn, Dept Mech Engn, Bursa, Turkey
[2] Uludag Univ, Vocat Sch Yenisehir I Orhan, Dept Air Conditioning & Ref, Bursa, Turkey
[3] Uludag Univ, Vocat Sch Gemlik A Kocabiyik, Dept Machinery, Bursa, Turkey
关键词
Double effect absorption; Refrigeration; Energy; Exergy; High pressure generator; 2ND LAW ANALYSIS; LITHIUM-BROMIDE; THERMODYNAMIC ANALYSIS; WATER; LIBR/H2O;
D O I
10.1016/j.enconman.2015.09.010
中图分类号
O414.1 [热力学];
学科分类号
摘要
Absorption refrigeration systems are environmental friendly since they can utilize industrial waste heat and/or solar energy. In terms of heat source of the systems, researchers prefer one type heat source usually such as hot water or steam. Some studies can be free from environment. In this study, energy and exergy analysis is performed on a double effect series flow absorption refrigeration system with water/lithium bromide as working fluid pair. The refrigeration system runs on various heat sources such as hot water, hot air and steam via High Pressure Generator (HPG) because of hot water/steam and hot air are the most common available heat source for absorption applications but the first law of thermodynamics may not be sufficient analyze the absorption refrigeration system and to show the difference of utilize for different type heat source. On the other hand operation temperatures of the overall system and its components have a major effect on their performance and functionality. In this regard, a parametric study conducted here to investigate this effect on heat capacity and exergy destruction of the HPG, coefficient of performance (COP) of the system, and mass flow rate of heat sources. Also, a comparative analysis is carried out on several heat sources (e.g. hot water, hot air and steam) in terms of exergy destruction and mass flow rate of heat source. From the analyses it is observed that exergy destruction of the HPG increases at higher temperature of the heat sources, condenser and absorber, and lower temperature of the HPG, LPG and evaporator. This destruction is maximized when hot air heat source is used and minimized with utilizing hot water heat source. (C) 2015 Elsevier Ltd. All rights reserved.
引用
收藏
页码:21 / 30
页数:10
相关论文
共 50 条
  • [1] Exergy analysis of double effect vapor absorption refrigeration system
    Khaliq, Abdul
    Kumar, Rajesh
    INTERNATIONAL JOURNAL OF ENERGY RESEARCH, 2008, 32 (02) : 161 - 174
  • [2] Energy and exergy analysis of single-effect absorption refrigeration system with different refrigerants
    Li J.
    Wang G.
    Xiong Y.
    Xu Q.
    Huagong Jinzhan/Chemical Industry and Engineering Progress, 2023, 42 : 104 - 112
  • [3] Exergy analysis of solar assisted double effect absorption refrigeration system
    Ravikumar, TS
    Suganthi, L
    Anand, AS
    RENEWABLE ENERGY, 1998, 14 (1-4) : 55 - 59
  • [4] Energy and exergy investigation of a novel double effect hybrid absorption refrigeration system for solar cooling
    Bouaziz, Nahla
    Lounissi, D.
    INTERNATIONAL JOURNAL OF HYDROGEN ENERGY, 2015, 40 (39) : 13849 - 13856
  • [5] ENERGY AND EXERGY ANALYSIS OF A DOUBLE EFFECT PARALLEL FLOW LIBR/H2O ABSORPTION REFRIGERATION SYSTEM
    Arora, Akhilesh
    Dixit, Manoj
    Kaushik, S. C.
    JOURNAL OF THERMAL ENGINEERING, 2016, 2 (01): : 541 - 549
  • [6] Energy and Exergy Analysis Study of Heat Exchanger in a Refrigeration System with Different Lengths of Capillary Tube
    Salem, Thamer Khalif
    Farhan, Saad Sami
    Farhan, Israa Sami
    INTERNATIONAL JOURNAL OF THERMODYNAMICS, 2020, 23 (04) : 260 - 266
  • [7] ENERGY AND EXERGY ANALYSIS OF ABSORPTION-COMPRESSION CASCADE REFRIGERATION SYSTEM
    Dixit, Manoj
    Kaushik, S. C.
    Arora, Akhilesh
    JOURNAL OF THERMAL ENGINEERING, 2016, 2 (06): : 995 - 1006
  • [8] Exergy analysis of a diffusion absorption refrigeration system
    Ben Jemaa, R.
    Ben Issa, N.
    Ben Issa, S.
    Bellagi, A.
    INTERNATIONAL JOURNAL OF EXERGY, 2008, 5 (5-6) : 626 - 637
  • [9] Energy and exergy analysis of vapor compression-triple effect absorption cascade refrigeration system
    Agarwal, Shyam
    Arora, Akhilesh
    Arora, B. B.
    ENGINEERING SCIENCE AND TECHNOLOGY-AN INTERNATIONAL JOURNAL-JESTECH, 2020, 23 (03): : 625 - 641
  • [10] Energy and exergy analyses of the diffusion absorption refrigeration system
    Yildiz, Abdullah
    Ersoz, Mustafa Ali
    ENERGY, 2013, 60 : 407 - 415