Review on the Characteristics, Heating Sources and Evolutionary Processes of the Operating Composite Insulators with Abnormal Temperature Rise

被引:27
|
作者
Yuan, Zhikang [1 ]
Tu, Youping [1 ]
Li, Ruihai [2 ]
Zhang, Fuzeng [2 ]
Gong, Bo [2 ]
Wang, Cong [1 ]
机构
[1] North China Elect Power Univ, State Key Lab Alternate Elect Power Syst Renewabl, Beijing 102206, Peoples R China
[2] China Southern Power Grid Co Ltd, Elect Power Res Inst, Guangzhou 510080, Peoples R China
来源
CSEE JOURNAL OF POWER AND ENERGY SYSTEMS | 2022年 / 8卷 / 03期
基金
中国国家自然科学基金;
关键词
Abnormal temperature rise; composite insulator; glass fiber reinforced plastic (GRP) core; silicone rubber housing; DECAY-LIKE FRACTURE; BRITTLE-FRACTURE; SILICONE-RUBBER; TESTING METHOD; GRP ROD; MECHANISM; INTERFACE; MOISTURE; WATER; CONTAMINATION;
D O I
10.17775/CSEEJPES.2019.02790
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
This paper reviews the research progress on abnormal temperature rise (ATR) of composite insulators. The ATR of composite insulators can be divided into two types, point-form temperature rise (PFTR) and bar-form temperature rise (BFTR). The composite insulators with PFTR only show significant temperature rise at high relative humidity (RH) (> 70%), and the temperature rise is located in the area that is 20 cm above the metal end-fitting. In a low humidity environment (< 30%), there is little temperature rise (< 1.0 K). The polarization loss on the surface of the silicone rubber housing under an AC electric field after moisture absorption is the main heating source. Corona discharge in high RH causes surface degradation of the silicone rubber. The composite insulators with BFTR shows significant temperature rise at both high (> 70%) and low (< 30%) RH. The temperature rise could reach more than 10 degrees C and the temperature rise area is wider, extending from the high-voltage end to several shed units at the low-voltage side. And the glass fiber reinforced plastic (GRP) core in the composite insulator is found to be corroded. The heating energy is supplied by both conductance loss and polarization loss of the corroded GRP core. The decay-like degradation of the GRP core is caused by the combination of damp conditions, high electric field, discharge, mechanical load, et al. and may evolve into a decay-like fracture of the composite insulator. The preventive methods concerning quality control, structure optimization, material modification and operational strategy are presented. It is suggested that when PFTR is detected on the composite insulator, the inspection period of the insulator should be properly shortened. The composite insulator should be replaced as soon as the BFTR was detected.
引用
收藏
页码:910 / 921
页数:12
相关论文
共 44 条
  • [21] Aging Characteristics of Interface Between Core and Sheath of Composite Insulators Under Water and High Temperature
    Nie Z.
    Wang L.
    Yang C.
    Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2018, 38 (15): : 4601 - 4611
  • [22] Analysis of Aging Characteristics of Umbrella Skirts of Composite Insulators Operating under the Influence of a Wind and Sand Environment in South Xinjiang
    Zhang, Xiaojun
    Kuang, Shilong
    Wu, Suzhou
    Zhuang, Wenbing
    He, Chunqing
    MATERIALS, 2024, 17 (03)
  • [23] The Quantitative Evaluation of Aging State of Field Composite Insulators Based on Trap Characteristics and Volume Resistivity-Temperature Characteristics
    Liang, Ying
    Gao, Li-Juan
    Dong, Ping-Ping
    Gao, Ting
    JOURNAL OF ELECTRICAL ENGINEERING & TECHNOLOGY, 2018, 13 (03) : 1355 - 1362
  • [24] An Intelligent Cable Core Temperature Abnormal Data Cleaning Method Considering Current-Carrying Temperature Rise Characteristics
    Hu Ran
    Li Bing
    Wang Jinyang
    Huang Siyong
    Lu Yihang
    Li Xianghao
    Yang Ling
    Wang Zhidong
    2022 12TH INTERNATIONAL CONFERENCE ON POWER AND ENERGY SYSTEMS, ICPES, 2022, : 1 - 5
  • [25] Integration of Renewable Energy Sources into Low-Temperature District Heating Systems: A Review
    Sarbu, Ioan
    Mirza, Matei
    Muntean, Daniel
    ENERGIES, 2022, 15 (18)
  • [26] Influence of vibration characteristics on temperature uniformity of particles during heating processes in a vibrationally fluidized bed
    Menbari, Amir
    Hashemnia, Kamyar
    POWDER TECHNOLOGY, 2022, 396 : 596 - 614
  • [27] Diagnosis Method of Decay-like Composite Insulators in a High-Humidity Environment Based on Characteristic Coefficient of Temperature Rise Gradient
    Zhang, Yuming
    Hou, Sizu
    Geng, Jianghai
    Gong, Yijing
    Zhong, Zheng
    POLYMERS, 2023, 15 (12)
  • [28] Temperature Rise Within the Pulp Chamber During Composite Resin Polymerisation Using Three Different Light Sources
    Santini, A.
    Watterson, C.
    Miletic, V.
    OPEN DENTISTRY JOURNAL, 2008, 2 : 137 - 141
  • [29] Investigation on the temperature rise characteristics of radio frequency heating considering water evaporation in low-rank coal
    Liu, Rui
    Dong, Xuelin
    Gao, Deli
    APPLIED THERMAL ENGINEERING, 2024, 257
  • [30] Hot Oil Carrying and Oil Film Temperature Rise Characteristics of Hydrostatic Thrust Bearings under Various Operating Conditions
    Zhang, Yan-Qin
    Feng, Ya-Nan
    Luo, Yi
    Yu, Xiao-Dong
    Tuijin Jishu/Journal of Propulsion Technology, 1600, 43 (05): : 254 - 263