Selection of the cooling system configuration for an ultra-critical coal-fired power plant

被引:9
作者
Wroblewski, Wlodzimierz [1 ]
Dykas, Slawomir [1 ]
Rulik, Sebastian [1 ]
机构
[1] Silesian Tech Univ, Inst Power Engn & Turbomachinery, PL-44100 Gliwice, Poland
关键词
Steam condenser; Serial condenser; Cooling system; HEI model; Exhaust loss; Condenser cost; Coal-fired power plant;
D O I
10.1016/j.enconman.2013.07.084
中图分类号
O414.1 [热力学];
学科分类号
摘要
The appropriate selection of the condenser pressure, apart from raising the live steam parameters, is a factor which could have a decisive impact on the improvement in the efficiency of the thermal cycle. The pressure value depends both on the parameters and configuration of the cooling system. The condenser cooling system configuration is particularly important in the case of newly designed high-capacity ultra-supercritical power plants. The presented study comprises a comparison of two variants of a cooling system for a 900 MW ultra-supercritical power unit. The serial and parallel configurations of the condenser are considered. A thermodynamic analysis which takes account of the exhaust loss of the LP turbine is performed. Additionally, an economic analysis based on the NPV method is conducted for all investigated cases. (C) 2013 Elsevier Ltd. All rights reserved.
引用
收藏
页码:554 / 560
页数:7
相关论文
共 13 条
[1]  
[Anonymous], 1981, United State Patent, Patent No. [4.306.418, 4306418]
[2]   Thermoeconomic optimization method as design tool in gas-steam combined plant realization [J].
Attala, L ;
Facchini, B ;
Ferrara, G .
ENERGY CONVERSION AND MANAGEMENT, 2001, 42 (18) :2163-2172
[3]   Effect of water side deposits on the energy performance of coal fired thermal power plants [J].
Bhatt, MS .
ENERGY CONVERSION AND MANAGEMENT, 2006, 47 (9-10) :1247-1263
[4]  
Cziesla F., 2009, LUNEN STATE OF THE A
[5]  
Cziesla F., 2009, ADV 800 MW STEAM POW
[6]  
Gardzilewicz A, 2008, TURBOMACHINERY, P133
[7]   The effect of the internal reheat application on the efficiency of the 900 MW ultra-supercritical coal-fired power unit [J].
Lukowicz, Henryk ;
Dykas, Slawomir ;
Stepczynska, Katarzyna ;
Rulik, Sebastian .
ARCHIVES OF THERMODYNAMICS, 2011, 32 (03) :127-144
[8]  
Peters M. S., 2003, PLANT DESIGN EC CHEM, V4
[9]   Reduction of CO2 emissions of coal fired power plants by optimizing steam water cycle [J].
Ploumen, Pierre ;
Stienstra, Gerard ;
Kamphuis, Hans .
10TH INTERNATIONAL CONFERENCE ON GREENHOUSE GAS CONTROL TECHNOLOGIES, 2011, 4 :2074-2081
[10]  
Pulman E., 2001, STEAM SURFACE CONDEN