Three-dimensional analysis of the effect of human movement on indoor airflow patterns

被引:38
作者
Bhattacharya, Arup [1 ]
Pantelic, Jovan [2 ]
Ghahramani, Ali [2 ,3 ]
Mousavi, Ehsan S. [1 ,2 ]
机构
[1] Clemson Univ, Dept Construct Sci & Management, 2-132 Lee Hall, Clemson, SC 29634 USA
[2] Univ Calif Berkeley, Ctr Built Environm, Berkeley, CA 94720 USA
[3] Natl Univ Singapore, Sch Design & Environm, Dept Bldg, Singapore, Singapore
关键词
3-D velocities; human movement; human-induced contamination; indoor airflow; infectious disease control; ultrasound sensor; AIRBORNE TRANSMISSION; VENTILATION; SIMULATION; MOTION; DOOR;
D O I
10.1111/ina.12735
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Human activity is known to leave significant effects on indoor airflow patterns. These patterns are carefully designed for many facilities such as cleanrooms, pharmaceutical settings, and healthcare environments, where human-induced wakes contribute to the transport of contaminants. Therefore, the knowledge about these wakes as it relates to indoor air quality is critical. As a result, a series of experiments were conducted in a controlled chamber to study the three-dimensional effects of true human walking on airflow. Experiments were designed to capture the effect of human walking under three different flow conditions, and for two different walking schemes. The results show that the effect of walking on the airflow is not negligible and can sustain up to 10 seconds after the moving body has passed. Walking on a straight line creates significant change in the velocity normal to the walking path and vertical to the plane of walking movement. These changes were detectable till 1.0 m away from the walking track. Also, the similarity between airflow patterns of walking once and twice illustrated a promising opportunity of predicting the flow patterns of random walk from a set of base cases.
引用
收藏
页码:587 / 601
页数:15
相关论文
共 47 条
[1]   Measuring 3D indoor air velocity via an inexpensive low -power ultrasonic anemometer [J].
Arens, Edward ;
Ghahramani, Ali ;
Przybyla, Richard ;
Andersen, Michael ;
Min, Syung ;
Peffer, Therese ;
Raftery, Paul ;
Zhu, Megan ;
Luu, Vy ;
Zhang, Hui .
ENERGY AND BUILDINGS, 2020, 211
[2]  
ASHRAE, 2013, VENT HLTH CAR FAC
[3]  
Awbi H.B., 2003, Ventilation of Buildings, V2nd
[4]   TESTING AND OPTIMIZING THE PERFORMANCE OF A FLOOR-BASED TASK CONDITIONING SYSTEM [J].
BAUMAN, FS ;
ARENS, EA ;
TANABE, S ;
ZHANG, H ;
BAHARLO, A .
ENERGY AND BUILDINGS, 1995, 22 (03) :173-186
[5]   The ventilation of multiple-bed hospital wards: Review and analysis [J].
Beggs, Clive B. ;
Kerr, Kevin G. ;
Noakes, Catherine J. ;
Hathway, E. Abigail ;
Sleigh, P. Andrew .
AMERICAN JOURNAL OF INFECTION CONTROL, 2008, 36 (04) :250-259
[6]   Particle dispersion in a cleanroom - effects of pressurization, door opening and traffic flow [J].
Bhattacharya, Arup ;
Metcalf, Andrew R. ;
Nafchi, Ali Mohammadi ;
Mousavi, Ehsan S. .
BUILDING RESEARCH AND INFORMATION, 2021, 49 (03) :294-307
[7]  
Bjorn E., 1997, P HLTH BUILDINGS 5 I, V2, P163
[8]   The effect of moving heat sources upon the stratification in rooms ventilated by displacement ventilation [J].
Brohus, H. ;
Balling, K. D. ;
Jeppesen, D. .
INDOOR AIR, 2006, 16 (05) :356-372
[9]   Modeling particle deposition on the surfaces around a multi-slot diffuser [J].
Chen, Chun ;
Lin, Chao-Hsin ;
Wei, Daniel ;
Chen, Qingyan .
BUILDING AND ENVIRONMENT, 2016, 107 :79-89
[10]   Experimental investigation into the interaction between the human body and room airflow and its effect on thermal comfort under stratum ventilation [J].
Cheng, Y. ;
Lin, Z. .
INDOOR AIR, 2016, 26 (02) :274-285