A new method for non-unit protection of power transmission lines based on fault resistance and fault angle reduction

被引:10
作者
Guo, Zhenwei [1 ,2 ]
Yao, Jiangang [1 ]
Yang, Shengjie [1 ]
Zhang, Hong [3 ]
Mao, Tian [1 ]
Thanh Long Duong [1 ]
机构
[1] Hunan Univ, Coll Elect & Informat Engn, Changsha 410082, Hunan, Peoples R China
[2] Shaoyang Univ, Dept Elect Engn, Shaoyang, Peoples R China
[3] Southeast Univ, Coll Elect Engn, Nanjing, Jiangsu, Peoples R China
关键词
Non-unit transient protection method; Energy difference of high-frequency transient current; Transition resistance; Fault angle; Single-phase fault; Power transmission lines; TRANSFORM;
D O I
10.1016/j.ijepes.2013.10.027
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In the paper, a new non-unit transient protection method suitable for single-phase faults of EHV power transmission lines was proposed based on the analysis of the propagation characteristics induced by fault transient current, the transition resistance and the fault angle on corresponding energy values of high-frequency transient current in extra high voltage (EHV) network. In the procedure, the transient current energy values from both sides of the bus were primarily normalized on the basis of transition resistance and fault angle, and then the characteristic value with functions of direction judge and value comparison was obtained by calculating their difference. By utilizing the characteristic value, the methodology came into being, by which the impacts of both transition resistance and fault angle were eliminated. The overall design has a high reliability level and owns twice the scope of the conventional protection. Simulations were performed and analyzed upon a three-phase 500 kV power system by utilizing ATP/EMTP, with various kinds of typical faults being taken into account. Plenty of results verify the feasibility of the algorithm for ultra-high speed protection of EHV power transmission lines. (C) 2013 Elsevier Ltd. All rights reserved.
引用
收藏
页码:760 / 769
页数:10
相关论文
共 26 条