A new method for recognizing internal faults from inrush current conditions in digital differential protection of power transformers

被引:51
作者
Golshan, MEH [1 ]
Saghaian-nejad, M [1 ]
Saha, A [1 ]
Samet, H [1 ]
机构
[1] Isfahan Univ Technol, Dept Elect & Comp Engn, Esfahan, Iran
关键词
transfonner differential protection; differential current components; inrush current; fault current; criterion function;
D O I
10.1016/j.epsr.2003.11.015
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In this paper. a new algorithnn based on processing differential current harmonics is proposed for digital differential protection of power transformers. This algorithm has been developed by considering different behaviors of second harmonic components of the differential currents under fault and inrush current conditions. In the new method, a criterion function is defined in terms of time variation of second harmonic of differential current. By evaluating the sign of the criterion function for the three phases, the internal faults can be accurately recognized from inrush current conditions about half cycle after the occurrence of disturbance, this is one advantage of the method. Another advantage of the proposed method is that the fault detection algorithm does not depend on the selection of thresholds. The suitable performance of this method will be demonstrated by simulation of different faults and switching conditions on a power transformer. For this purpose, a small part of Iran power system involving a power transformer and the transmission lines on both sides of the transformer has been considered. To include effective factors on differential current components, the elements of this power system have been precisely modeled in PSCAD/EMTDC. (C) 2004 Elsevier B.V All rights reserved.
引用
收藏
页码:61 / 71
页数:11
相关论文
共 8 条
[1]   NEURAL-NETWORK-BASED ALGORITHM FOR POWER TRANSFORMER DIFFERENTIAL RELAYS [J].
BASTARD, P ;
MEUNIER, M ;
REGAL, H .
IEE PROCEEDINGS-GENERATION TRANSMISSION AND DISTRIBUTION, 1995, 142 (04) :386-392
[2]  
GIULIANTE A, 1991, P GEORG TECHN PROT R, P1
[3]  
Guzman A, 2000, SEL TECHNICAL PAPERS, P405
[4]  
INAGAKI K, 1998, TPWRD3 IEEE, V4, P1501
[5]  
ROCKEFELLER GD, 1969, TPAS98 IEEE, P438
[6]  
SIDHU TS, 1992, TPWRD7 IEEE, V4, P1885
[7]   A MULTICRITERIA DIFFERENTIAL TRANSFORMER RELAY BASED ON FUZZY-LOGIC [J].
WISZNIEWSKI, A ;
KASZTENNY, B .
IEEE TRANSACTIONS ON POWER DELIVERY, 1995, 10 (04) :1786-1792
[8]   Power differential method for discrimination between fault and magnetizing inrush current in transformers [J].
Yabe, K .