Simulation and experimental analysis of optimal buried depth of the vertical U-tube ground heat exchanger for a ground-coupled heat pump system

被引:56
作者
Chen, Jinhua [1 ,2 ]
Xia, Lei [1 ,2 ]
Li, Baizhan [1 ,2 ]
Mmereki, Daniel [3 ]
机构
[1] Chongqing Univ, Natl Ctr Int Res Low Carbon & Green Bldg, Chongqing 400045, Peoples R China
[2] Chongqing Univ, Key Lab Gorges Reservoir Reg Ecoenvironm 3, Chongqing 400045, Peoples R China
[3] Chongqing Univ, Civil Engn Rover Stn, Chongqing 400045, Peoples R China
关键词
Ground-coupled heat pump; Heat transfer model; Heat exchange rate; Optimal buried depth; PERFORMANCE; MODEL;
D O I
10.1016/j.renene.2014.06.007
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
This paper presents a numerical heat transfer model for vertical U-tube Ground Heat Exchangers (GHE). This model is uniquely able to take into to account different initial soil temperatures and physical properties at different depths. The model has been validated based on an experimental case study and has been used to simulate the thermal performance of GHEs. The simulation results show that for a 100-m vertical GHE, the first 70 m of the vertically buried GHE has a higher heat transfer capability than its last 30-m section. In addition, the validated model is used to investigate the optimal depth of vertical GHEs in five case studies ranging from 60 to 100 m length. Among them, the simulation results demonstrate that the GHE with buried depth of 70 m is able to provide the highest heat exchange rate per unit depth (54.1 and 47.0 W/m under heat rejection/extraction mode). It consequently results in shortest total GHE length of 11,388 m and the minimum cost of 1.82 million Yuan. However, a larger area is needed for boreholes and GHEs installation. Therefore, the optimal buried depth of the vertical U-tube GHEs for the studied case is 70 m on the condition of allocation of an abundant area to set up the boreholes. (C) 2014 Elsevier Ltd. All rights reserved.
引用
收藏
页码:46 / 54
页数:9
相关论文
共 18 条
  • [1] Ball DavidA., 1983, ASHRAE T, V89, P416
  • [2] Analysis of thermal and dynamic comportment of a geothermal vertical U-tube heat exchanger
    Bouhacina, Benamar
    Saim, Rachid
    Benzenine, Hamidou
    Oztop, Hakan F.
    [J]. ENERGY AND BUILDINGS, 2013, 58 : 37 - 43
  • [3] Carslaw HS, 1946, CONDUCTION HEAT SOLI, P260
  • [4] CARSLAW HS, 1959, CONDUCTION HEAT SOLI, P260
  • [5] Temperature distributions in boreholes of a vertical ground-coupled heat pump system
    Esen, Hikmet
    Inalli, Mustafa
    Esen, Yuksel
    [J]. RENEWABLE ENERGY, 2009, 34 (12) : 2672 - 2679
  • [6] ESKILSON P, 1987, THESIS U LUND LUND
  • [7] Fujun W, 2004, DYNAMICS ANAL COMPUT
  • [8] Guo Kaisheng, 2010, THESIS CHONGQING U
  • [9] Performance study of a ground heat exchanger based on the multipole theory heat transfer model
    Hu, Pingfang
    Yu, Zhongyi
    Zhu, Na
    Lei, Fei
    Yuan, Xudong
    [J]. ENERGY AND BUILDINGS, 2013, 65 : 231 - 241
  • [10] Ingersoll L.R., 1954, Heat Conduction: With Engineering, Geological, and Other Applications, V2nd