Impact of demand controlled ventilation on system performance and energy use

被引:24
作者
Delwati, Muhannad [1 ,4 ]
Merema, Bart [2 ]
Breesch, Hilde [2 ]
Helsen, Lieve [1 ,3 ]
Sourbron, Maarten [1 ]
机构
[1] Katholieke Univ Leuven, Dept Mech Engn, Celestijnenlaan 300, B-3001 Leuven, Belgium
[2] Katholieke Univ Leuven, Dept Civil Engn, Construct Technol Cluster, Ghent, Belgium
[3] EnergyVille, Thor Pk, Waterschei, Genk, Belgium
[4] Katholieke Univ Leuven, Dept Architecture, Kasteelpk Arenberg 1, B-3001 Leuven, Belgium
基金
欧盟地平线“2020”;
关键词
Demand controlled ventilation; Ventilation system performance; Fan energy use; Pressure set point; Control strategies; Trim & respond;
D O I
10.1016/j.enbuild.2018.06.015
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Demand-controlled-ventilation (DCV) refers to a ventilation system with controlled air flow rate based on indoor air quality. DCV operates at reduced air flow rates during most of the operation time. Therefore, less energy is required for fan operation, compared to a constant-air-volume (CAV) ventilation system. Typically, DCV has a two-layer control with variable-air-volume (VAV) valves, and a fan speed control to maintain a constant-static-pressure in the duct system based on a pressure set point. However, this nominal design based fan pressure setpoint is higher than required when all VAV-valves are closed to a certain extent. Therefore, advanced pressure-reset (PR) control - resetting the pressure set point - potentially reduces fan energy use even further. This paper assesses the impact of fan control on both fan energy use and ventilation performance in DCV system of a densely occupied office. Results of a simulation model and realistic measurement setup are compared. The PR control, using air flow rate and VAV-valve position measurements as feedback, causes significantly reduction on fan energy use. These reductions compared to conventional DCV and CAV respectively, are approximately 10% and 72% in case of high occupancy and 50% and 93% in case of low occupancy. Largely, DCV with PR control is strongly considered, especially when occupancy is often expected to deviate significantly from the nominal conditions. Moreover, both simulations and measurements show that there is a clear trade-off between air flow rate deficit and fan energy use, when the fan energy use is lower, the air flow rate deficit is higher and vice versa. Furthermore, the results show that VAV-valve accuracy, characteristics and its lower operational limit hamper the ventilation system in achieving the predicted performance as in the simulation. (C) 2018 Elsevier B.V. All rights reserved.
引用
收藏
页码:111 / 123
页数:13
相关论文
共 13 条
[1]   Demand controlled ventilation indoor climate and energy performance in a high performance building with air flow rate controlled chilled beams [J].
Ahmed, Kaiser ;
Kurnitski, Jarek ;
Sormunen, Piia .
ENERGY AND BUILDINGS, 2015, 109 :115-126
[2]  
[Anonymous], 2012, EN13799 IEA CBECS
[3]  
Baetens R., 2015, P BUILDING SIMULATIO
[4]  
Braun JE, 2003, VSAT VENTILATION STR
[5]  
Brooks PJ, 2010, ASHRAE J, V52, P30
[6]  
Koulani C. S., 2014, P 35 AIVC C AIR INF
[7]   Demand controlled ventilation (DCV) in school and office buildings: Lessons learnt from case studies [J].
Merema, Bart ;
Delwati, Muhannad ;
Sourbron, Maarten ;
Breesch, Hilde .
ENERGY AND BUILDINGS, 2018, 172 :349-360
[8]  
Murphy J, 2011, ASHRAE J, V53, P18
[9]  
Taylor ST, 2007, ASHRAE J, V49, P24
[10]  
Taylor ST, 2015, ASHRAE J, V57, P52