A heuristic meter placement method for load estimation

被引:16
作者
Liu, HJ [1 ]
Yu, D
Chiang, HD
机构
[1] Cooper Power Syst, Thomas A Edison Tech Ctr, Franksville, WI 53126 USA
[2] Univ Wisconsin, Dept Elect Engn, Milwaukee, WI 53201 USA
[3] Cornell Univ, Sch Elect Engn, Ithaca, NY 14853 USA
关键词
heuristic method; load estimation; meter placement; power distribution planning;
D O I
10.1109/TPWRS.2002.801040
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
A heuristic method of optimal meter placement for load estimation in distribution systems is presented in this paper. The approach can be used to efficiently find the meter location candidates for load estimation. The meter placement method presented in this paper has a two-stage approach. In the first stage, meters are placed using a heuristic method. In the second stage, the confidence interval is calculated to determine if the meters give satisfactory results when loads vary between the maximum and minimum. Sample system analysis and testing results show the approach is efficient for finding tentative meter locations. Real application constraints such as meter failure backup, availability of space, automated switch locations, and unbalanced systems, also are considered. The meter placement method for load estimation can be easily extended to place meters for circuit state estimation (SE).
引用
收藏
页码:913 / 917
页数:5
相关论文
共 8 条
[1]   A METER PLACEMENT METHOD FOR STATE ESTIMATION [J].
BARAN, ME ;
ZHU, JX ;
ZHU, HB ;
GARREN, KE .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1995, 10 (03) :1704-1710
[2]   STATE ESTIMATION FOR REAL-TIME MONITORING OF DISTRIBUTION-SYSTEMS [J].
BARAN, ME ;
KELLEY, AW .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1994, 9 (03) :1601-1609
[3]   NETWORK RECONFIGURATION IN DISTRIBUTION-SYSTEMS FOR LOSS REDUCTION AND LOAD BALANCING [J].
BARAN, ME ;
WU, FF .
IEEE TRANSACTIONS ON POWER DELIVERY, 1989, 4 (02) :1401-1407
[4]   Meter placement for real-time monitoring of distribution feeders [J].
Baran, ME ;
Zhu, JX ;
Kelley, AW .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1996, 11 (01) :332-337
[5]   Load modeling for distribution circuit state estimation [J].
Ghosh, AK ;
Lubkeman, DL ;
Jones, RH .
IEEE TRANSACTIONS ON POWER DELIVERY, 1997, 12 (02) :999-1005
[6]  
Heydt G. T., 1986, Computer Analysis Methods For Power Systems
[7]   Improving feeder voltage calculation results with telemetered data [J].
Leou, RC ;
Lu, CN .
IEEE TRANSACTIONS ON POWER DELIVERY, 1996, 11 (04) :1914-1920
[8]   OPTIMAL SELECTION OF CAPACITORS FOR RADIAL DISTRIBUTIONS SYSTEMS USING A GENETIC ALGORITHM [J].
SUNDHARARAJAN, S ;
PAHWA, A .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1994, 9 (03) :1499-1507