A Fault Isolation Method via Classification and Regression Tree-Based Variable Ranking for Drum-Type Steam Boiler in Thermal Power Plant

被引:7
|
作者
Yu, Jungwon [1 ]
Jang, Jaeyel [2 ]
Yoo, Jaeyeong [3 ]
Park, June Ho [1 ]
Kim, Sungshin [1 ]
机构
[1] Busan Natl Univ, Dept Elect & Comp Engn, Busan 46241, South Korea
[2] Korea East West Power Co Ltd, Tech Solut Ctr, Technol & Informat Dept, Dangjin 31700, South Korea
[3] XEONET Co Ltd, CTO, Seongnam 13216, South Korea
关键词
drum-type steam boiler; fault isolation; classification and regression tree; variable ranking; smearing effect; INDEPENDENT COMPONENT ANALYSIS; FISHER DISCRIMINANT-ANALYSIS; IDENTIFICATION APPROACH; DIAGNOSIS; MODEL; NETWORKS; TUBE;
D O I
10.3390/en11051142
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Accurate detection and isolation of possible faults are indispensable for operating complex industrial processes more safely, effectively, and economically. In this paper, we propose a fault isolation method for steam boilers in thermal power plants via classification and regression tree (CART)-based variable ranking. In the proposed method, binary classification trees are constructed by applying the CART algorithm to a training dataset which is composed of normal and faulty samples for classifier learning then, to perform faulty variable isolation, variable importance values for each input variable are extracted from the constructed trees. The importance values for non-faulty variables are not influenced by faulty variables, because the values are extracted from the trees with decision boundaries only in the original input space; the proposed method does not suffer from smearing effect. Furthermore, the proposed method, based on the nonparametric CART classifier, can be applicable to nonlinear processes. To confirm the effectiveness, the proposed and comparison methods are applied to two benchmark problems and 250 MW drum-type steam boiler. Experimental results show that the proposed method isolates faulty variables more clearly without the smearing effect than the comparison methods.
引用
收藏
页数:19
相关论文
共 1 条
  • [1] A Clustering-Based Fault Detection Method for Steam Boiler Tube in Thermal Power Plant
    Yu, Jungwon
    Jang, Jaeyel
    Yoo, Jaeyeong
    Park, June Ho
    Kim, Sungshin
    JOURNAL OF ELECTRICAL ENGINEERING & TECHNOLOGY, 2016, 11 (04) : 848 - 859