A comparison of heating terminal units: Fan-coil versus radiant floor, and the combination of both

被引:55
作者
Atienza Marquez, Antonio [1 ]
Cejudo Lopez, Jose Manuel [1 ]
Fernandez Hernandez, Francisco [1 ]
Dominguez Munoz, Fernando [1 ]
Carrillo Andres, Antonio [1 ]
机构
[1] Univ Malaga, ETSII, Energy Res Grp, C Doctor Pedro Ortiz Ramos S-N, Malaga 29013, Spain
关键词
Radiant floor; Fan-coil; Control; Heating combined system; MODEL-PREDICTIVE CONTROL; SYSTEMS;
D O I
10.1016/j.enbuild.2016.12.092
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Several control strategies are compared for a hydronic heating system that combines two different terminal units, radiant floor and fan-coil, in the same thermal zone. The performance of the combined system is evaluated in terms of energy consumption and comfort level. The production unit is an air-water heat pump. Four control strategies are defined and compared using a TRNSYS model: one strategy is applied when only the radiant floor operates, two strategies (simply and improved) are applied when only the fan-coil operates, and one strategy is applied when both terminal units operate simultaneously. Simulations are undertaken for three major cities with different heating requirements. In terms of comfort, the combined system achieves the higher scores, ensuring comfort conditions during most of the heating season. In terms of energy consumption, the worst option is the one that uses a fan-coil with fixed air velocity and fixed inlet water temperature. Nonetheless, there are not important differences between the analysed control options. The energy consumption of the system is mainly influenced by the part load performance of the heat pump, although the differences are small. (C) 2016 Elsevier B.V. All rights reserved.
引用
收藏
页码:621 / 629
页数:9
相关论文
共 17 条
[1]   Theory and applications of HVAC control systems - A review of model predictive control (MPC) [J].
Afram, Abdul ;
Janabi-Sharifi, Farrokh .
BUILDING AND ENVIRONMENT, 2014, 72 :343-355
[2]  
[Anonymous], 2005, 77302005 SO
[3]  
[Anonymous], 2004, 55 ASHRAE
[4]  
[Anonymous], 2008, AHSRAE SYSTEMS ATLAN
[5]  
Backman C., 2013, AIR TO WATER HEAT PU
[6]  
Beghi A, 2011, IEEE INTL CONF CONTR, P258, DOI 10.1109/CCA.2011.6044398
[7]   Energy-efficient control of under-actuated HVAC zones in commercial buildings [J].
Brooks, Jonathan ;
Kumar, Saket ;
Goyal, Siddharth ;
Subramany, Rahul ;
Barooah, Prabir .
ENERGY AND BUILDINGS, 2015, 93 :160-168
[8]  
Daikin, 2016, HEAT TECHN INF DAIK
[9]   Generalised water flow rate control strategy for optimal part load operation of ground source heat pump systems [J].
Edwards, K. C. ;
Finn, D. P. .
APPLIED ENERGY, 2015, 150 :50-60
[10]   Partial load performance test of residential heat pump system with low-GWP refrigerants [J].
In, Sungjin ;
Cho, Keumnam ;
Lim, Byunghan ;
Lee, Changseon .
APPLIED THERMAL ENGINEERING, 2015, 85 :179-187