共 4 条
Study concerning production of lighting overvoltages on low-voltage power distribution lines
被引:0
作者:
Taniguchi, H
[1
]
Sugimoto, H
Yokoyama, S
机构:
[1] Hokuriku Elect Power Co, Toyama, Japan
[2] CRIEPI, Tokyo, Japan
关键词:
low-voltage power distribution lines;
lightning overvoltage;
indirect lightning stroke;
direct lightning strike;
lightning-resistant design;
D O I:
10.1002/(SICI)1520-6416(200003)130:4<66::AID-EEJ8>3.0.CO;2-H
中图分类号:
TM [电工技术];
TN [电子技术、通信技术];
学科分类号:
0808 ;
0809 ;
摘要:
In order to study lightning problems of low-voltage power distribution lines, lightning overvoltage waveforms were observed inside the homes of customers. The cause of lightning overvoltages was examined from observation of striking points by still cameras. Lightning overvoltages of 62 waveforms were recorded by observation over a period of about 3 in years. Observed waveforms can be classified into three types of single polarity (positive or negative), both polarities (which change from positive to negative or negative to positive), and pulsive waveform. The causes of these lightning overvoltages which were estimated from striking points are shown as follows: (1) Induced lightning overvoltages on low-voltage distribution lines. (2) Electric potential rise due to discharge of surge arresters or current of overhead ground wire. (3) Shift of lightning overvoltages from high-voltage side of transformer to low-voltage side, which is due to electromagnetic induction. (C) 2000 Scripta Technica.
引用
收藏
页码:66 / 75
页数:10
相关论文