Partial Discharge Detection and Localization in Power Transformers based on Acoustic Emission: Theory, Methods, and Recent Trends

被引:25
作者
Rathod, Viral B. [1 ]
Kumbhar, Ganesh B. [1 ]
Bhalja, Bhavesh R. [1 ]
机构
[1] Indian Inst Technol, Dept Elect Engn, Roorkee, Uttar Pradesh, India
关键词
Acoustic emission (AE); acoustic method; electrical method; localization; partial discharge (PD); power transformer; propagation; time difference of arrival (TDOA); LOCATION;
D O I
10.1080/02564602.2021.1871672
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper provides a comprehensive review of the acoustic method used for partial discharge (PD) localization in power transformer. The paper outlines the partial discharge mechanism, basic principle and properties of the acoustic emission (AE), advantages and limitations of the acoustic method compared to the electrical method, and different AE based PD localization techniques along with their algorithms used in power transformer. Most of the algorithms proposed in the literature for PD localization in power transformer are based on the time difference of arrival (TDOA) of AE signals. Thus, this paper would help researchers, academicians, and engineering communities working in the area of AE based PD localization in power transformer to avoid insulation damage.
引用
收藏
页码:540 / 552
页数:13
相关论文
共 61 条
  • [1] Akiyoshi D.F., 2018, EVALUATION LOW COST, V4, P36, DOI 10.3390/ecsa-5-05722
  • [2] ALMASRI WMF, 2016, IEEE T INSTRUM MEAS, V65
  • [3] [Anonymous], 2019, IEEE STAND SAF LEV R, DOI 10.1109/IEEESTD.2019.8859679
  • [4] [Anonymous], 2016, IEC 62478
  • [5] [Anonymous], 2000, IEC 60270:2000, V3
  • [6] ANTONY D, 2018, IEEE T POWER DELIVER, V33
  • [7] AVZAYESH M, IEEE T INSTRUM MEAS, V69
  • [8] Bartnikas R., 1979, ENG DIELECTRICS
  • [9] BISWAS S, 2012, IEEE T DIELECTR ELEC, V19
  • [10] BOYA C, 2015, IEEE T DIELECTR ELEC, V22