Research on Heat Recovery Technology for Reducing the Energy Consumption of Dedicated Ventilation Systems: An Application to the Operating Model of a Laboratory

被引:9
作者
Zhang, Lian [1 ,2 ]
Zhang, Yu Feng [1 ]
机构
[1] Tianjin Univ, Sch Environm Sci & Engn, Tianjin 300072, Peoples R China
[2] Tianjin Sino German Vocat Tech Coll, Sch Elect & Energy, Tianjin 300350, Peoples R China
来源
ENERGIES | 2016年 / 9卷 / 01期
关键词
heat pipe heat exchanger (HPHX); fresh air (FA); energy saving; thermal comfort; EXCHANGER; PIPE; PERFORMANCE; AIR;
D O I
10.3390/en9010024
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
In this research, the application of heat pipes in the air handler dedicated to decoupling dehumidification from cooling to reduce energy consumption was simulated and investigated by simulations and experimental studies. The cooling load profiles and heat pipes with effectiveness of 0.45 and 0.6, respectively, were evaluated in achieving the desired space conditions and calculated hour by hour. The results demonstrated that for all examined cases, a heat pipe heat exchanger (HPHX) can be used to save over 80% of the energy during the hours of operation of air conditioning. The overall energy reduction rate was from 3.2% to 4.5% under air conditioning system conditions. It was found that the energy saving potential of a laboratory was higher than for other kinds of buildings. Therefore, the dedicated ventilation system combined with heat recovery technology can be efficiently applied to buildings, especially for laboratories in subtropical areas.
引用
收藏
页数:20
相关论文
共 24 条
  • [1] The application of heat pipe heat exchangers to improve the air quality and reduce the energy consumption of the air conditioning system in a hospital ward-A full year model simulation
    Ahmadzadehtalatapeh, M.
    Yau, Y. H.
    [J]. ENERGY AND BUILDINGS, 2011, 43 (09) : 2344 - 2355
  • [2] Alexander D.K., 1997, HTB2 USER MANUAL VER
  • [3] Effects of Thermal Mass, Window Size, and Night-Time Ventilation on Peak Indoor Air Temperature in the Warm-Humid Climate of Ghana
    Amos-Abanyie, S.
    Akuffo, F. O.
    Kutin-Sanwu, V.
    [J]. SCIENTIFIC WORLD JOURNAL, 2013,
  • [4] Calautit J.K., 2015, RENEW ENERGY
  • [5] *EL MECH SERV DEP, 2002, HONG KONG EN END US
  • [6] Model-based optimal control of a dedicated outdoor air-chilled ceiling system using liquid desiccant and membrane-based total heat recovery
    Ge, Gaoming
    Xiao, Fu
    Xu, Xinhua
    [J]. APPLIED ENERGY, 2011, 88 (11) : 4180 - 4190
  • [7] Investigation on a ventilation heat recovery exchanger: Modeling and experimental validation in dry and partially wet conditions
    Gendebien, Samuel
    Bertagnolio, Stephane
    Lemort, Vincent
    [J]. ENERGY AND BUILDINGS, 2013, 62 : 176 - 189
  • [8] Investigation of Performance of Heat Pipe as Heat Exchanger Using Alternative Refrigerants
    Hassan, M. A. M.
    [J]. JOURNAL OF ENERGY ENGINEERING-ASCE, 2013, 139 (01): : 18 - 24
  • [9] Passive energy recovery from natural ventilation air streams
    Hughes, Ben Richard
    Chaudhry, Hassam Nasarullah
    Calautit, John Kaiser
    [J]. APPLIED ENERGY, 2014, 113 : 127 - 140
  • [10] Lee WL, 2001, BUILD SERV ENG RES T, V22, P113